Inspections for the day of: Tuesday, November 22, 2005.
Number of inspections: 30
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-02432 FIRE-Final Inspection11/22/200511/22/200511/22/2005 7:12:13 PMPFAIL
Lower the height of the provided fire extinguisher to 48" AFF, provide missing sprinkler escutcheon, remove tape from heads in the restrooms, provide additional emergency light in the back room as discussed.
FIR05-00684 INSP-Alarm Testing11/21/200511/22/200511/22/2005 7:08:26 PMPPART
Addressing for the duct smoke detectors does not match approved plans, provide resubmittals reflecting correct numbers and locations, all other items tested okay, final pending resubmittals and shell alarm final.
BLD05-02358 FIRE-Final Inspection11/21/200511/22/200511/22/2005 7:01:09 PMPCANC
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
BLD05-01831 FIRE-Final Inspection11/22/200511/22/200511/22/2005 7:00:13 PMPCANC
FIR05-00681 INSP-Final Inspection11/22/200511/22/200511/22/2005 6:59:25 PMPPART
Fire sprinkler work is satisfactory, final pending shell sprinkler final approval.
FIR05-00076 INSP-Alarm Testing11/22/200511/22/200511/22/2005 6:57:02 PMPCANC
FIR05-00666 INSP-Alarm Testing11/21/200511/22/200511/22/2005 6:56:37 PMPCANC
BLD05-00458 FIRE-Final Inspection11/22/200511/22/200511/22/2005 4:09:10 PMPPART
Fire alarm must be finaled prior to life safety final approval, items on c/n must be completed as required.
FIR05-00595 INSP-Final Inspection11/22/200511/22/200511/22/2005 4:05:41 PMAPART
Inspection to be performed by M. Froemke. Resubmittals are required as the Plan Modification approved submittal does not match the installed system.

Tested all items except the duct and in-duct detctors. (Requested magnehelic test on all duct detectors as locations are in the 90's of the duct work.)
FIR05-00198 INSP-Final Inspection11/21/200511/22/200511/22/2005 4:04:20 PMPCANC
No time available for this inspection today.
FIR05-00796 INSP-Final Inspection11/21/200511/22/200511/22/2005 4:03:43 PMPCANC
Inspection to be performed tomorrow per agreement.
BLD05-01956 FIRE-Final Inspection11/22/200511/22/200511/22/2005 4:02:37 PMPNR
c/n not 100% completed yet per contractor.
FIR05-00577 INSP-Final Inspection11/21/200511/22/200511/22/2005 4:00:50 PMPCANC
No time available for this inspection today.
FIR05-00577 INSP-Sprinkler Rough-in/Hydro11/21/200511/22/200511/22/2005 4:00:13 PMPCANC
No time for this inspection today.
FIR05-00576 INSP-Final Inspection11/21/200511/22/200511/22/2005 3:59:23 PMPPART
Basement alarm tested okay, 1st floor testing not completed due to an AHU malfunction.
FIR05-00453 INSP-Final Inspection11/22/200511/22/200511/22/2005 3:57:13 PMPPASS
Fire alarm permit work passed inspection.
FIR05-00577 INSP-Sprinkler Rough-in/Hydro11/18/200511/22/200511/22/2005 1:46:44 PMACANC
No time for this inspection today.
MIS05-00210 FIR-Final11/22/200511/22/200511/22/2005 11:58:31 AMAPART
Life safety appears satisfactory, however the approved plans and related MIS permit paperwork were not available on site for review or verification of project scope.
BLD05-00322 FIRE-Final Inspection11/21/200511/22/200511/22/2005 11:56:01 AMAFAIL
The exit discharge lights failed to function, provide approved hardware for the pocket doors at the confrence room as required.
BLD05-01956 FIRE-Final Inspection11/18/200511/22/200511/22/2005 11:27:21 AMANR
Per contractor phone call, not all items on the correction notice have been completed.
FIR05-00595 INSP-Final Inspection11/21/200511/22/200511/22/2005 11:24:12 AMADEFR
Inspection to be performed by M. Froemke.
FIR05-00618 INSP-Final Inspection11/21/200511/22/200511/22/2005 11:23:10 AMADEFR
Inspection to be performed by M. Froemke.
BLD05-01899 FIRE-Final Inspection11/21/200511/22/200511/22/2005 11:21:21 AMAPASS
Fire life safety passed inspection.
BLD05-01345 FIRE-Final Inspection11/21/200511/22/200511/22/2005 10:45:32 AMAPASS
The related fire alarm permit has been finaled. Fire life safety is acceptable for permanent occupancy.
FIR05-00369 INSP-Final Inspection11/21/200511/22/200511/22/2005 10:43:38 AMAPASS
The duct detectors have been relocated and tested satisfactory, fire alarm permit finaled.
FIR05-00326 INSP-Final Inspection11/21/200511/22/200511/22/2005 10:05:04 AMAPASS
Correction notice items have been completed, submit as-builts reflecting pipe routing changes as required.
FIR05-00718 INSP-Final Inspection11/21/200511/22/200511/22/2005 10:02:41 AMAFAIL
The approved stamped plans must be on site for the inspection to be completed.
FIR05-00718 INSP-Sprinkler Rough-in/Hydro11/21/200511/22/200511/22/2005 10:01:04 AMAFAIL
The approved stamped plans were not available on site for review, these documents must be available for inspection to be completed.
FIR05-00618 INSP-Final Inspection11/22/200511/22/200511/22/2005 12:00:00 AMPCANC
Resubmittal required on single station visible/audible room on first floor. No inspections until plans are issued.
FIR05-00489 INSP-Conference11/16/200511/22/200511/18/2005 1:43:28 PMACANC
Phone #: ###-#### Internet Inspection Request from: Rob Puckett Inspection cancelled from web by: Rob Puckett