BLD05-02432
| FIRE-Final Inspection | 11/22/2005 | 11/22/2005 | 11/22/2005 7:12:13 PM | P | FAIL |
|
|
Lower the height of the provided fire extinguisher to 48" AFF, provide missing sprinkler escutcheon, remove tape from heads in the restrooms, provide additional emergency light in the back room as discussed.
|
FIR05-00684
| INSP-Alarm Testing | 11/21/2005 | 11/22/2005 | 11/22/2005 7:08:26 PM | P | PART |
|
|
Addressing for the duct smoke detectors does not match approved plans, provide resubmittals reflecting correct numbers and locations, all other items tested okay, final pending resubmittals and shell alarm final.
|
BLD05-02358
| FIRE-Final Inspection | 11/21/2005 | 11/22/2005 | 11/22/2005 7:01:09 PM | P | CANC |
|
|
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD05-01831
| FIRE-Final Inspection | 11/22/2005 | 11/22/2005 | 11/22/2005 7:00:13 PM | P | CANC |
|
|
|
FIR05-00681
| INSP-Final Inspection | 11/22/2005 | 11/22/2005 | 11/22/2005 6:59:25 PM | P | PART |
|
|
Fire sprinkler work is satisfactory, final pending shell sprinkler final approval.
|
FIR05-00076
| INSP-Alarm Testing | 11/22/2005 | 11/22/2005 | 11/22/2005 6:57:02 PM | P | CANC |
|
|
|
FIR05-00666
| INSP-Alarm Testing | 11/21/2005 | 11/22/2005 | 11/22/2005 6:56:37 PM | P | CANC |
|
|
|
BLD05-00458
| FIRE-Final Inspection | 11/22/2005 | 11/22/2005 | 11/22/2005 4:09:10 PM | P | PART |
|
|
Fire alarm must be finaled prior to life safety final approval, items on c/n must be completed as required.
|
FIR05-00595
| INSP-Final Inspection | 11/22/2005 | 11/22/2005 | 11/22/2005 4:05:41 PM | A | PART |
|
|
Inspection to be performed by M. Froemke. Resubmittals are required as the Plan Modification approved submittal does not match the installed system.
Tested all items except the duct and in-duct detctors. (Requested magnehelic test on all duct detectors as locations are in the 90's of the duct work.)
|
FIR05-00198
| INSP-Final Inspection | 11/21/2005 | 11/22/2005 | 11/22/2005 4:04:20 PM | P | CANC |
|
|
No time available for this inspection today.
|
FIR05-00796
| INSP-Final Inspection | 11/21/2005 | 11/22/2005 | 11/22/2005 4:03:43 PM | P | CANC |
|
|
Inspection to be performed tomorrow per agreement.
|
BLD05-01956
| FIRE-Final Inspection | 11/22/2005 | 11/22/2005 | 11/22/2005 4:02:37 PM | P | NR |
|
|
c/n not 100% completed yet per contractor.
|
FIR05-00577
| INSP-Final Inspection | 11/21/2005 | 11/22/2005 | 11/22/2005 4:00:50 PM | P | CANC |
|
|
No time available for this inspection today.
|
FIR05-00577
| INSP-Sprinkler Rough-in/Hydro | 11/21/2005 | 11/22/2005 | 11/22/2005 4:00:13 PM | P | CANC |
|
|
No time for this inspection today.
|
FIR05-00576
| INSP-Final Inspection | 11/21/2005 | 11/22/2005 | 11/22/2005 3:59:23 PM | P | PART |
|
|
Basement alarm tested okay, 1st floor testing not completed due to an AHU malfunction.
|
FIR05-00453
| INSP-Final Inspection | 11/22/2005 | 11/22/2005 | 11/22/2005 3:57:13 PM | P | PASS |
|
|
Fire alarm permit work passed inspection.
|
FIR05-00577
| INSP-Sprinkler Rough-in/Hydro | 11/18/2005 | 11/22/2005 | 11/22/2005 1:46:44 PM | A | CANC |
|
|
No time for this inspection today.
|
MIS05-00210
| FIR-Final | 11/22/2005 | 11/22/2005 | 11/22/2005 11:58:31 AM | A | PART |
|
|
Life safety appears satisfactory, however the approved plans and related MIS permit paperwork were not available on site for review or verification of project scope.
|
BLD05-00322
| FIRE-Final Inspection | 11/21/2005 | 11/22/2005 | 11/22/2005 11:56:01 AM | A | FAIL |
|
|
The exit discharge lights failed to function, provide approved hardware for the pocket doors at the confrence room as required.
|
BLD05-01956
| FIRE-Final Inspection | 11/18/2005 | 11/22/2005 | 11/22/2005 11:27:21 AM | A | NR |
|
|
Per contractor phone call, not all items on the correction notice have been completed.
|
FIR05-00595
| INSP-Final Inspection | 11/21/2005 | 11/22/2005 | 11/22/2005 11:24:12 AM | A | DEFR |
|
|
Inspection to be performed by M. Froemke.
|
FIR05-00618
| INSP-Final Inspection | 11/21/2005 | 11/22/2005 | 11/22/2005 11:23:10 AM | A | DEFR |
|
|
Inspection to be performed by M. Froemke.
|
BLD05-01899
| FIRE-Final Inspection | 11/21/2005 | 11/22/2005 | 11/22/2005 11:21:21 AM | A | PASS |
|
|
Fire life safety passed inspection.
|
BLD05-01345
| FIRE-Final Inspection | 11/21/2005 | 11/22/2005 | 11/22/2005 10:45:32 AM | A | PASS |
|
|
The related fire alarm permit has been finaled. Fire life safety is acceptable for permanent occupancy.
|
FIR05-00369
| INSP-Final Inspection | 11/21/2005 | 11/22/2005 | 11/22/2005 10:43:38 AM | A | PASS |
|
|
The duct detectors have been relocated and tested satisfactory, fire alarm permit finaled.
|
FIR05-00326
| INSP-Final Inspection | 11/21/2005 | 11/22/2005 | 11/22/2005 10:05:04 AM | A | PASS |
|
|
Correction notice items have been completed, submit as-builts reflecting pipe routing changes as required.
|
FIR05-00718
| INSP-Final Inspection | 11/21/2005 | 11/22/2005 | 11/22/2005 10:02:41 AM | A | FAIL |
|
|
The approved stamped plans must be on site for the inspection to be completed.
|
FIR05-00718
| INSP-Sprinkler Rough-in/Hydro | 11/21/2005 | 11/22/2005 | 11/22/2005 10:01:04 AM | A | FAIL |
|
|
The approved stamped plans were not available on site for review, these documents must be available for inspection to be completed.
|
FIR05-00618
| INSP-Final Inspection | 11/22/2005 | 11/22/2005 | 11/22/2005 12:00:00 AM | P | CANC |
|
|
Resubmittal required on single station visible/audible room on first floor. No inspections until plans are issued.
|
FIR05-00489
| INSP-Conference | 11/16/2005 | 11/22/2005 | 11/18/2005 1:43:28 PM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Rob Puckett Inspection cancelled from web by: Rob Puckett
|