Inspections for the day of: Wednesday, November 22, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-04010 Permanent Service11/22/200611/22/200611/23/2006 10:43:03 AMPPASS
Scheduled by a contractor via Hello! on 11/22/2006 at 7:37:09 AM. Contact: ###-####. u/g new for meter ok
ELE06-03743 Electrical Rough-In11/21/200611/22/200611/22/2006 3:42:01 PMAPART
this is for a ceiling inspection, any questions please call Steve Nuxoll; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ceilings ok as noted on green sticker talked with Steve about clearence for panel exception made for clearence 110.26 per J Frank
ELE06-03489 Final11/21/200611/22/200611/22/2006 2:59:52 PMAPASS
jared ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok card signed survey needs box extenions recep desk area, bond hot and cold water
ELE06-03925 Final11/22/200611/22/200611/22/2006 2:58:53 PMPPASS
daryl ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok
ELE06-02181 Final11/22/200611/22/200611/22/2006 2:12:49 PMPNH
Phone #: ###-#### Internet Inspection Request from: Matt Santacruz notice posted
ELE06-04140 Conference11/22/200611/22/200611/22/2006 1:55:38 PMPDONE
kelly - please call 1/2 hr prior to inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia ok
ELE06-04110 Electrical Rough-In11/21/200611/22/200611/22/2006 1:55:18 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton ok corr. made
ELE06-03308 Final11/22/200611/22/200611/22/2006 12:06:46 PMPFAIL
mitch ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called no access and ceiling covered before inspection
ELE06-04357 Temporary Service11/21/200611/22/200611/22/2006 9:20:03 AMAFAIL
BULLETT; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
corr called 110.12, clean t/s needs plastic conn for GEC, gfci for 230V recept
ELE06-03185 Permanent Service11/21/200611/22/200611/22/2006 8:52:36 AMAFAIL
WE ARE READY FOR PERM. SERVICE. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corr. called 250.24(C) shall install neutral conductor from meter to p/s not grd wire, 250.30(A)(7) shall install GEC from xformer to u/g copper water not p/s panel bus, 210.5 (A B C ) ID 480/277 120/208 at all locations as code noted states, shall not use tie wraps for flex
ELE06-04365 Final11/21/200611/22/200611/22/2006 8:05:11 AMAPASS
any questions please call Dan Wright; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok card signed
ELE06-02456 Final11/21/200611/22/200611/22/2006 7:47:03 AMAPASS
garage code 2245; Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ok