ELE06-04010
| Permanent Service | 11/22/2006 | 11/22/2006 | 11/23/2006 10:43:03 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 11/22/2006 at 7:37:09 AM. Contact: ###-####. u/g new for meter ok
|
ELE06-03743
| Electrical Rough-In | 11/21/2006 | 11/22/2006 | 11/22/2006 3:42:01 PM | A | PART |
|
|
this is for a ceiling inspection, any questions please call Steve Nuxoll; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ceilings ok as noted on green sticker talked with Steve about clearence for panel exception made for clearence 110.26 per J Frank
|
ELE06-03489
| Final | 11/21/2006 | 11/22/2006 | 11/22/2006 2:59:52 PM | A | PASS |
|
|
jared ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok card signed survey needs box extenions recep desk area, bond hot and cold water
|
ELE06-03925
| Final | 11/22/2006 | 11/22/2006 | 11/22/2006 2:58:53 PM | P | PASS |
|
|
daryl ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok
|
ELE06-02181
| Final | 11/22/2006 | 11/22/2006 | 11/22/2006 2:12:49 PM | P | NH |
|
|
Phone #: ###-#### Internet Inspection Request from: Matt Santacruz notice posted
|
ELE06-04140
| Conference | 11/22/2006 | 11/22/2006 | 11/22/2006 1:55:38 PM | P | DONE |
|
|
kelly - please call 1/2 hr prior to inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia ok
|
ELE06-04110
| Electrical Rough-In | 11/21/2006 | 11/22/2006 | 11/22/2006 1:55:18 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton ok corr. made
|
ELE06-03308
| Final | 11/22/2006 | 11/22/2006 | 11/22/2006 12:06:46 PM | P | FAIL |
|
|
mitch ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called no access and ceiling covered before inspection
|
ELE06-04357
| Temporary Service | 11/21/2006 | 11/22/2006 | 11/22/2006 9:20:03 AM | A | FAIL |
|
|
BULLETT; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr called 110.12, clean t/s needs plastic conn for GEC, gfci for 230V recept
|
ELE06-03185
| Permanent Service | 11/21/2006 | 11/22/2006 | 11/22/2006 8:52:36 AM | A | FAIL |
|
|
WE ARE READY FOR PERM. SERVICE. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corr. called 250.24(C) shall install neutral conductor from meter to p/s not grd wire, 250.30(A)(7) shall install GEC from xformer to u/g copper water not p/s panel bus, 210.5 (A B C ) ID 480/277 120/208 at all locations as code noted states, shall not use tie wraps for flex
|
ELE06-04365
| Final | 11/21/2006 | 11/22/2006 | 11/22/2006 8:05:11 AM | A | PASS |
|
|
any questions please call Dan Wright; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok card signed
|
ELE06-02456
| Final | 11/21/2006 | 11/22/2006 | 11/22/2006 7:47:03 AM | A | PASS |
|
|
garage code 2245; Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ok
|