Inspections for the day of: Wednesday, November 22, 2006.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03089 Electrical Rough-In11/22/200611/22/200611/22/2006 4:17:53 PMPPASS
joe ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith u/g ok to cover, gec ok, review what needed for ri
ELE06-03920 Electrical Rough-In11/22/200611/22/200611/22/2006 3:55:52 PMPPASS
paul Note: kitchen; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles east side, kitchen and den area ok to cover
ELE06-04308 Electrical Rough-In11/22/200611/22/200611/22/2006 2:35:47 PMPPASS
daryl - call for access ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith walls and hard lids only ok to cover
ELE06-03378 Final11/21/200611/22/200611/22/2006 2:24:09 PMPPASS
Final - questions pls call Mike w/Doherty @ ###-####. Scheduled by Heather w/Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer corr made, ok to final, signed card
ELE06-03185 Permanent Service11/22/200611/22/200611/22/2006 2:20:19 PMPPASS
we are ready for a reinspection for perm. service. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corr made, p/s u/g n ok
ELE06-04359 Final11/22/200611/22/200611/22/2006 1:17:16 PMPPASS
questions pls call Mike w/Doherty @ ###-####. Scheduled by Heather w/Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer t/s ok to final, see t/s
ELE06-04359 Temporary Service11/22/200611/22/200611/22/2006 1:16:40 PMPPASS
questions pls call Mike w/Doherty @ ###-####. Scheduled by Heather w/Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer corr made, t/s o/h n ok
ELE06-03814 Final11/21/200611/22/200611/22/2006 10:54:24 AMAPASS
KEVIN; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
ELE06-00628 Final11/22/200611/22/200611/22/2006 10:39:18 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot ok to final
ELE05-04498 Final11/22/200611/22/200611/22/2006 10:35:55 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot told elect, left corr notice, nec 110.26(A)(1) shall have 36" work depth in front of panels
ELE06-04359 Final11/21/200611/22/200611/22/2006 9:34:51 AMAFAIL
temp power insp. questions pls call Mike w/Doherty @ ###-####. Scheduled by Heather w/Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer called, left corr notice, nec 230.74 service disc shall disconnect all ungrounded conductors simultaneously,312.5 shall provide abrasion protection for all conductors entering enclosure, 250.53(G) electrode shall be flush with or below ground, 408.4 circuit directory shall be correct, BCC job id sticker shall be posted
ELE06-03704 Permanent Service11/21/200611/22/200611/22/2006 9:30:51 AMAPASS
insp for street lights. Questions pls call Mike w/Doherty @ ###-####. Scheduled by Heatherw/Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer p/s u/g n ok
ELE06-03360 Electrical Rough-In11/21/200611/22/200611/22/2006 9:05:05 AMAPASS
joe ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to cover ceilings
ELE06-03529 Electrical Rough-In11/21/200611/22/200611/22/2006 8:46:25 AMAPASS
jeff; Phone #: ###-#### Internet Inspection Request from: Patricia Smith walls and hard lids only ok to cover
ELE05-02003 Final11/21/200611/22/200611/22/2006 8:06:41 AMAPART
Scheduled by a contractor via Hello! on 11/21/2006 at 1:29:29 PM. 3rd fl anop ok to final
ELE06-04110 Electrical Rough-In11/21/200611/22/200611/21/2006 4:34:10 PMACANC
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton