ELE11-01932
| ELE-Aging Inspection | 11/22/2013 | 11/22/2013 | 11/25/2013 4:24:51 PM | | DONE |
|
|
Unable to make contact
|
ELE11-00879
| ELE-Aging Inspection | 11/22/2013 | 11/22/2013 | 11/25/2013 4:16:52 PM | | DONE |
|
|
Still under construction
|
ELE13-03284
| Electrical Rough-In | 11/22/2013 | 11/22/2013 | 11/22/2013 4:28:45 PM | P | PASS |
|
|
Please call 30 minutes prior John ###-#### Phone #: ###-#### >> Inspection requested via web by John VanZandt Rough in ok cover
|
ELE13-02203
| Final | 11/22/2013 | 11/22/2013 | 11/22/2013 3:48:09 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by mike brown Final ok
|
ELE13-02258
| Final | 11/21/2013 | 11/22/2013 | 11/22/2013 3:12:05 PM | P | FAIL |
|
|
Call general contractor to allow entrance into house Phone #: ###-#### >> Inspection requested via web by John Harvey 210.8- All 120 volt receptical outlets shall have GFCI protection. 110.3- 2 receptical outlets in family room do not work. 210.8- All bath receptical outlets shall have GFCI protection. 210.52- At least 1 receptical outlet shall be located with in 36" of basin and outside cabinet. 410.16 Luminaire located in closets shall have minimum of 6" clearence from shelf. 314.20- Boxes located in tile recessed more than 1/4" shall have box extenders installed. 408.4- Garage panel schedule shall be labelled.
|
ELE13-03256
| Final | 11/21/2013 | 11/22/2013 | 11/22/2013 2:25:59 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Brad Girard Completed corrections for permit # ele13-01371. Final ok
|
ELE13-01371
| Final | 11/22/2013 | 11/22/2013 | 11/22/2013 2:25:08 PM | P | PASS |
|
|
Corrections completed see permit #ele13-03256. Final ok
|
ELE13-03277
| Final | 11/21/2013 | 11/22/2013 | 11/22/2013 2:10:36 PM | A | PASS |
|
|
Please provide rough-in of ceiling and final. Thank you! Phone #: ###-#### >> Inspection requested via web by Dan Wright Final ok
|
ELE13-03277
| Electrical Rough-In | 11/22/2013 | 11/22/2013 | 11/22/2013 2:10:21 PM | P | CANC |
|
|
Please provide rough-in of ceiling and final. Thank you! Phone #: ###-#### >> Inspection requested via web by Dan Wright Rough in ok cover
|
ELE13-02807
| Final | 11/21/2013 | 11/22/2013 | 11/22/2013 1:52:16 PM | A | PASS |
|
|
please call before you head over so I can make sure space is unlocked.
Thanks Phone #: ###-#### >> Inspection requested via web by Tyler Bowen Final ok
|
ELE13-02830
| Electrical Rough-In | 11/22/2013 | 11/22/2013 | 11/22/2013 1:51:29 PM | P | NR |
|
|
Contact: Wes Powell ###-#### >> Inspection requested via web by Deb Gooden Contractor to check if ceiling structure manufacturers specs allow for support of wiring to be attached.
|
ELE13-02654
| Electrical Rough-In | 11/22/2013 | 11/22/2013 | 11/22/2013 1:48:15 PM | A | PASS |
|
|
Danny. Wall & soffit cover. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Control room wall, bar 1/2 wall, bar structrural soffit, private dining structrural soffits rough in ok cover
|
ELE13-02577
| Electrical Rough-In | 11/22/2013 | 11/22/2013 | 11/22/2013 1:46:14 PM | A | PASS |
|
|
Danny. Ceiling cover. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Complete ceiling rough in ok cover
|
ELE13-02578
| Electrical Rough-In | 11/22/2013 | 11/22/2013 | 11/22/2013 1:45:30 PM | A | PASS |
|
|
Danny. Ceiling cover. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Complete ceiling rough in ok cover
|
GCE13-00183
| GCE-Rough-In | 11/22/2013 | 11/22/2013 | 11/22/2013 9:49:43 AM | P | PASS |
|
|
Jim ###-#### Rough in ok cover
|
ELE13-02810
| Electrical Rough-In | 11/21/2013 | 11/22/2013 | 11/22/2013 9:02:51 AM | A | PASS |
|
|
Ground inspection SE edge of property. Contact is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery Perimeter underground to 3 pole lights and front compressor. rough in ok cover
|