Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02982 Electrical Rough-In11/22/201611/22/201611/22/2016 3:10:40 PMPFAIL
Garbage compactors and Container winch motors Disconnect Locations and Use of Cords in lieu of fixed wiring Article 400 EM stops Phone #: ###-#### Inspection requested via web by Tom Betty
400.8(2)- Flexible cord for the hydraulic control shall not be run thru floor of platform. Shall be protected from physical damage. Rest of winches, disconnecting means, wiring methods ok
ELE16-03805 Electrical Rough-In11/21/201611/22/201611/22/2016 2:01:20 PMAPASS
House is empty. Lock box code is 8340 Inspection requested via web by Barbara Szurgot
Bedroom areas noted on BLD rough in ok cover
ELE16-03157 Final11/21/201611/22/201611/22/2016 12:24:25 PMAFAIL
Phone #: ###-#### Inspection requested via web by kendall bender
210.8(B)- All 120 volt receptacle outlets located in prep area shall have GFCI protection as stated in note 1 and 8 on print. 400.5- Flexible cord ampacity. #10 SJOOW flexible cord installed on expresso machines as per table 400.5 column B 30 amp max, 50 amp installed.
406.5(E)- Receptacle outlets shall not be installed face up in counter top surfaces unless specifically listed for area.
ELE16-01838 Final11/21/201611/22/201611/22/2016 11:12:49 AMAPART
Call Brandon for levels 1 through 4 Annex final sign off of TCO. Phone #: ###-#### Inspection requested via web by Tom Betty
210.8- 4th floor water heater 41E 8, 10, 12, GFCI devices shall be readily accessible.
Receptacle near dishwasher shall be GFCI protected.
422.30- Womens bath label switch located in stall up high as to its purpose.
110.3- Items to be connected as per manufacturers instructions. 2nd floor center podium floor box reverse polarity, Furniture in stadium jumpers missing. S. E. corner rows 2, 3, 5, 6. Floor boxes need trimmed N. offices and out 4 total.
TCO ok
ELE15-01348 Final11/21/201611/22/201611/22/2016 11:06:07 AMAPART
Call Brandon for levels 1 through 4 Annex TCO sign off. Phone #: ###-#### Inspection requested via web by Tom Betty 5th floor elevator control room,foyer, center rm gutter covers missing where gutter enters walls and above ceiling. Fire caulked with out cover mounted in elevator foyer. TCO ok