NAF17-00071
| INSP-Final | 11/21/2017 | 11/22/2017 | 11/22/2017 1:53:44 PM | A | DONE |
|
|
Life safety passed
|
FIR17-00364
| INSP-Alarm Testing | 11/21/2017 | 11/22/2017 | 11/22/2017 1:19:07 PM | A | FAIL |
|
|
Todays inspection was for the Pharmacy Rooms. A chime needs to be added to meet sound requirements prior to work being completed in this area.
|
FIR17-00545
| INSP-Sprinkler Rough-in | 11/22/2017 | 11/22/2017 | 11/22/2017 1:17:04 PM | P | PART |
|
|
The earth quake bracing in the corridor has been corrected. Pendant heads are still overspaced in the Laundry Room. The piping in the Corridor can be covered.
|
FIR17-00541
| INSP-Sprinkler Rough-in | 11/22/2017 | 11/22/2017 | 11/22/2017 11:12:25 AM | P | PASS |
|
|
See the city approved plans for locations inspected today where the rough-in was passed. I noted missing siesmic bracing for the branchlines, one missing lateral main bracing and one pendant head overspaced.
Rick Phone #: ###-####
|
NAF17-00059
| INSP-Final | 11/21/2017 | 11/22/2017 | 11/22/2017 9:56:19 AM | A | DONE |
|
|
Life safety passed
|