ELE19-03357
| Final | 11/22/2019 | 11/22/2019 | 11/22/2019 2:14:36 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by jamie berg Name plate missing on exterior of mobile home. Assume rating is in manufacturers instructions as per 550.11(D) exception. Chassis bond in place. Final ok
|
ELE19-03356
| Final | 11/22/2019 | 11/22/2019 | 11/22/2019 2:07:02 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by jamie berg Unable to locate name plate on mobile home. Assume rating is in manufacturers instructions in compliance with 550.11(D) exception. Chasis bond in place. Final ok
|
ELE19-04541
| Final | 11/22/2019 | 11/22/2019 | 11/22/2019 1:31:44 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Idsinga Led lighting retro, occ sensors, emergency lighting complete. Final ok
|
ELE19-04542
| Final | 11/22/2019 | 11/22/2019 | 11/22/2019 1:29:26 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Idsinga No interior lighting improvement, No sink in warehouse area where supplies and drains are in place. Emergency and egress lighting final ok
|
ELE19-04239
| Electrical Rough-In | 11/21/2019 | 11/22/2019 | 11/22/2019 12:10:08 PM | A | PASS |
|
|
Geoff Hannaford is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Walls and hard lids rough in ok cover
|
ELE19-04240
| Electrical Rough-In | 11/21/2019 | 11/22/2019 | 11/22/2019 11:53:20 AM | A | PASS |
|
|
Geoff Hannaford is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Walls and hard lids rough in ok cover
|
ELE19-04394
| Rough-In Permanent Service | 11/21/2019 | 11/22/2019 | 11/22/2019 11:10:02 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by danny perrine 110.3- Recessed can covers shall be installed tightly to junction boxes. North garage mud room, north spare bed. 250.64(D)(1)- Grounding electrode conductor shall have an external tap and extend to each service disconnect, 250.148- Metal boxes shall be connected to an equipment grounding conductor. 300.4- Nail plates needed in south garage marked with X. 300.15- NM cables shall terminate in a box. Recess can in utility make up missed. 334.12- NM cables shall not be installed where subject to damage. North garage HRs cut corner due to drywall nailer missing.
|
ELE19-00601
| Electrical Rough-In | 11/22/2019 | 11/22/2019 | 11/22/2019 10:03:42 AM | A | PASS |
|
|
2nd floor common area cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Level 2 corridor walls and fire lid rough in ok cover.
|
ELE19-04124
| Electrical Rough-In | 11/21/2019 | 11/22/2019 | 11/22/2019 9:20:16 AM | A | PASS |
|
|
Ceiling inspection please. Thank you and have a bless weekend!!! Phone #: ###-#### Inspection requested via web by Kyle Lott Grid rough in ok cover
|
ELE19-02808
| Electrical Rough-In | 11/21/2019 | 11/22/2019 | 11/22/2019 9:19:36 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mike McCarrel Discussed receptacle locations in face up positions. As per 406.5(E),(F), and (H)- restrictions for counter top, work areas, and seating areas. Tasting bar soffits and duct pocket walls rough in ok cover
|