Inspections for the day of: Friday, November 22, 2019.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00831 INSP-Sprinkler Rough-in11/21/201911/22/201911/22/2019 3:11:27 PMPPASS
The underground supply piping is ok for cover.

Jonathan Phone #: ###-####
BLD19-02178 FIRE-Final Inspection11/22/201911/22/201911/22/2019 11:47:44 AMPPASS
Life safety passed.

Randy Phone #: ###-#### PLEASE CALL FOR ACCESS
FIR19-00492 INSP-Sprinkler Rough-in/Hydro11/21/201911/22/201911/22/2019 11:42:44 AMAFAIL
Went to job site first thing as discussed but found the guage on 0psi. I left a message on George's phone and sent picture of guage. George Jess is the contact for this underground Hydro. He is hoping for an appointment in the AM before Troy has to leave. Thanks so much. Phone #: ###-#### Inspection requested via web by Stan Beus
BLD18-01534 FIRE-Final Inspection11/21/201911/22/201911/22/2019 10:31:06 AMAPASS
Life safety passed.

Dave Phone #: ###-####
FIR19-00613 INSP-Sprinkler Rough-in11/21/201911/22/201911/22/2019 10:09:27 AMAPASS
See the city approved plans for area where piping is ok for cover.

Jon Beazer is the contact for this RTC inspection. Thank you for your help. We appreciate it. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00859 INSP-Final Inspection11/21/201911/22/201911/22/2019 9:40:54 AMAFAIL
I met Richard on site and we found that someone had tampered with his suppression equipment. Was not able to test.

Phone #: 2086157641 >> Inspection requested via mobile web by Richard Johnson
FIR19-00686 INSP-Final Inspection11/21/201911/22/201911/22/2019 8:12:46 AMAFAIL
Provide plan mods showing the two changes of the wall mouted strobes to higher candella. Provide sync'ing of the audible/horn as per NFPA 72 18.4.2.4 and 3.3.317.1.

We are requesting the final for 7:30 because there are several restaurants and businesses that could be affected when alarm is set off. Thank You. Phone #: ###-#### Inspection requested via web by Sam Ball