FIR19-00394
| INSP-Final Inspection | 11/22/2019 | 11/22/2019 | 11/22/2019 3:08:31 PM | P | PASS |
|
|
Final underground supply inspection is complete.
|
BLD19-04531
| FIRE-Final Inspection | 11/22/2019 | 11/22/2019 | 11/22/2019 3:08:04 PM | P | PASS |
|
|
No fire sprinkler modifications (Tenant space is partially covered by fire sprinklers, inspection tag for what is there is current), no fire alarm modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for temp occupancy complete.
Call ahead // Ralph Phone #: ###-####
|
FIR19-00554
| INSP-Final Inspection | 11/21/2019 | 11/22/2019 | 11/22/2019 1:09:36 PM | A | PASS |
|
|
Final fire sprinkler inspection is complete, wiring for irrigation shutdown is correct as of this entry.
Call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD17-04372
| FIRE-Final Inspection | 11/21/2019 | 11/22/2019 | 11/22/2019 12:07:07 PM | A | PASS |
|
|
Final life fire safety inspection for racking system complete, will verify fire extinguisher placement during final life fire safety inspection.
Call Jeff 20 min before Phone #: ###-#### Inspection requested via web by Jeff Higgins
|
BLD19-04414
| FIRE-Conference | 11/22/2019 | 11/22/2019 | 11/22/2019 11:27:26 AM | A | DONE |
|
|
Fire conference is complete, fire aalrm notification will be required in conference room (Room 209 is a conference room, not an office as shown on city approved drawings) and breakroom, a seperate permit is required for any and all fire alarm modifications. Sprinkler heads in main lobby for tenant space are 155 degree heads and are less than 12 inches from heat registers, heads will need to be changed to intermediate temperature sprinkler heads. Fire extinguishers to be mounted in discussed locations.
|
BLD19-04414
| FIRE-Final Inspection | 11/21/2019 | 11/22/2019 | 11/22/2019 11:22:55 AM | A | CANC |
|
|
Request was for a conference, not a final inspection, this request is cancelled.
Please call for access- Ian Phone #: ###-####
|
FIR19-00658
| INSP-Conference | 11/21/2019 | 11/22/2019 | 11/22/2019 10:57:58 AM | A | DONE |
|
|
Fire conference complete, per conversation with Lee Meridith, Fire Alarm Plan Reviewer, due to the requirement of audio and visual effect shutdown on general fire the karaoke rooms will have strobe only as shown on city approved drawings. Both visual effects and audio in karaoke rooms will need to cease during general fire alarm activation as discussed, city approved plans need to reflect the addition of required device for audio and visual effect shutdown.
Request for consult for Friday late morning. Damien will call Jim tomorrow to coordinate the time. Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
BLD18-03243
| FIRE-Final Inspection | 11/22/2019 | 11/22/2019 | 11/22/2019 10:16:12 AM | A | PART |
|
|
Partial final inspection for life fire safety inspection complete. Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Items to inspect before final sign off are internally illuminated exit signs placed on exterior gates as discussed, place a class K fire extinguisher is kitchen per building permit fire code review comments, verify motion sensor operation on mag locks, south main entry, place map at fire panel with floor plan and location of initiating devices. Per conversation with Joe Bruce, Fire Section Supervisor, a 30 day TCO is authorized for life fire safety.
|
BLD18-03243
| FIRE-Conference | 11/21/2019 | 11/22/2019 | 11/22/2019 10:12:07 AM | A | DONE |
|
|
Fire conference complete.
Really need Fire and life safety! No line item for that inspection! Thanks! Phone #: ###-#### Inspection requested via web by Scott Simons
|
BLD19-04012
| FIRE-Final Inspection | 11/22/2019 | 11/22/2019 | 11/22/2019 9:19:15 AM | A | PART |
|
|
Partial final inspection for life fire safety complete, per conversation with Ron Johson with Boise Fire, a 45 day TCO is authorized for occupancy, final sign off is contingent upon items noted on the 21NOV2019 inspection being completed, inspected and finaled.
|
FIR19-00066
| INSP-Final Inspection | 11/21/2019 | 11/22/2019 | 11/22/2019 8:16:00 AM | A | PASS |
|
|
Final fire alarm inspection complete.
Phone #: ###-#### Inspection requested via web by Ken Webster
|
BLD19-03504
| FIRE-Final Inspection | 11/22/2019 | 11/22/2019 | 11/22/2019 7:45:10 AM | A | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete, signatures provided for associated trades on permit card.
|
FIR19-00844
| INSP-Final Inspection | 11/20/2019 | 11/22/2019 | 11/22/2019 7:44:00 AM | A | PASS |
|
|
Final fire alarm inspection for scope of work complete.
Call me to discuss the moring final, City has requested a 7am bells and whistles extravaganza. Cheers! NT Phone #: ###-#### Inspection requested via web by Neal Timmerman
|