FIR04-00414
| INSP-Final Inspection | 11/19/2004 | 11/23/2004 | 11/23/2004 12:00:00 AM | A | FAIL |
|
|
Test duct smoke detectors. Provide knox box. Provide signage on door. Multiple pull stations are mounted above 48". See review note #13. Provide a/v in conference room 116 per review note #5. Break room a/v needs to be 30cd to meet code. See approved plans for smoke detector locations that are within 3' of supply diffusers. Resubmit plans showing the two additional duct smoke detectors. Signals are messed up at the monitoring station. All zones need to be retested. Inspection stopped due to amount of items found to be incorrect. There may be additional items when re-inspected. 11/23/2004 10:05:14 AM
|
FIR04-00368
| INSP-Sprinkler Rough-in | 11/22/2004 | 11/23/2004 | 11/23/2004 12:00:00 AM | A | FAIL |
|
|
Tenting still is not done correctly. Still need the letter from the engineer 11/23/2004 11:03:06 AM
|
BLD03-02970
| FIRE-Final Inspection | 11/23/2004 | 11/23/2004 | 11/23/2004 12:00:00 AM | P | PASS |
|
|
fire life safety finaled 11/23/2004 1:14:51 PM
|
BLD04-01995
| FIRE-Final Inspection | 11/23/2004 | 11/23/2004 | 11/23/2004 12:00:00 AM | P | PASS |
|
|
Life safety passed. Per plans and Carl Westfall no emergency lighting is required. 11/23/2004 3:00:39 PM
|
BLD04-02386
| FIRE-Final Inspection | 11/23/2004 | 11/23/2004 | 11/23/2004 12:00:00 AM | P | CANC |
|
|
To be rescheduled for next week 11/23/2004 3:27:11 PM
|
BLD04-01953
| FIRE-Final Inspection | 11/23/2004 | 11/23/2004 | 11/23/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 11/23/2004 3:16:09 PM
|
BLD04-00027
| FIRE-Final Inspection | 11/23/2004 | 11/23/2004 | 11/23/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled
|
BLD04-00028
| FIRE-Final Inspection | 11/23/2004 | 11/23/2004 | 11/23/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled
|
BLD04-00026
| FIRE-Final Inspection | 11/23/2004 | 11/23/2004 | 11/23/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled
|