Inspections for the day of: Wednesday, November 23, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04250 Temporary Service11/23/200511/23/200511/23/2005 4:04:01 PMPFAIL
###-####-chris called contr, left corr notice, 408.38 panel shall be dead front,312.5 conductors entering enclosure shall have abrasion protection,250.52(A)(5)(b) ground rod shall be 5/8" diameter, fee due
ELE05-04249 Temporary Service11/23/200511/23/200511/23/2005 3:40:23 PMPFAIL
###-####-chris called contr, left corr notice, 312.5 conductors entering enclosures shall have abrasion protection, 250.52(A)(5)(b) ground rod shall be 5/8" diameter, fee due
ELE05-04248 Temporary Service11/23/200511/23/200511/23/2005 3:34:07 PMPFAIL
###-####-chris called contr, left corr notice, 312.5 conductors entering enclosures shall be protected from abrasion, 112.(C) there shall be no broken parts, 250.52(A)(5)(b) ground rod shall be 5/8" diameter, fee due
ELE05-03655 Rough-In Permanent Service11/22/200511/23/200511/23/2005 1:59:23 PMPPASS
Scheduled by a contractor via Hello! on 11/22/2005 at 11:19:36 AM. Contact: ###-####. ric ok, p/s u/g n ok
ELE05-03661 Final11/23/200511/23/200511/23/2005 1:54:43 PMPPART
Scheduled by a contractor via Hello! on 11/23/2005 at 9:39:37 AM. Contact: ###-####. signed temp occ card, contr has a few items left, switch in computer room, a few ballasts, panel schedules, couple switch cover, low voltage bushings
ELE05-04125 Temporary Service11/23/200511/23/200511/23/2005 12:04:40 PMPPASS
vivian; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corr made, t/s o/h n ok
ELE05-04246 Rough-In Permanent Service11/22/200511/23/200511/23/2005 10:19:59 AMAPASS
Charlie; Phone #: ###-#### Internet Inspection Request from: Melyne Davis ric ok, p/s u/g n ok
ELE05-03534 Electrical Rough-In11/23/200511/23/200511/23/2005 9:29:17 AMPPASS
Ceiling inspection; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson corrections made, clg cover ok
ELE05-04010 Electrical Rough-In11/23/200511/23/200511/23/2005 9:10:52 AMAPASS
Scheduled by a contractor via Hello! on 11/23/2005 at 7:29:25 AM. Contact: ###-####. ric ok, corrections made
ELE05-03097 Final11/22/200511/23/200511/23/2005 8:13:52 AMAPASS
daryl; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final
ELE05-03924 Electrical Rough-In11/22/200511/23/200511/23/2005 8:12:33 AMAPASS
WET NICHE LIGHTING ON A SWIMMING POOL; Phone #: ###-#### Internet Inspection Request from: Barry Kendall potting ok