ELE05-04250
| Temporary Service | 11/23/2005 | 11/23/2005 | 11/23/2005 4:04:01 PM | P | FAIL |
|
|
###-####-chris called contr, left corr notice, 408.38 panel shall be dead front,312.5 conductors entering enclosure shall have abrasion protection,250.52(A)(5)(b) ground rod shall be 5/8" diameter, fee due
|
ELE05-04249
| Temporary Service | 11/23/2005 | 11/23/2005 | 11/23/2005 3:40:23 PM | P | FAIL |
|
|
###-####-chris called contr, left corr notice, 312.5 conductors entering enclosures shall have abrasion protection, 250.52(A)(5)(b) ground rod shall be 5/8" diameter, fee due
|
ELE05-04248
| Temporary Service | 11/23/2005 | 11/23/2005 | 11/23/2005 3:34:07 PM | P | FAIL |
|
|
###-####-chris called contr, left corr notice, 312.5 conductors entering enclosures shall be protected from abrasion, 112.(C) there shall be no broken parts, 250.52(A)(5)(b) ground rod shall be 5/8" diameter, fee due
|
ELE05-03655
| Rough-In Permanent Service | 11/22/2005 | 11/23/2005 | 11/23/2005 1:59:23 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 11/22/2005 at 11:19:36 AM. Contact: ###-####. ric ok, p/s u/g n ok
|
ELE05-03661
| Final | 11/23/2005 | 11/23/2005 | 11/23/2005 1:54:43 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 11/23/2005 at 9:39:37 AM. Contact: ###-####. signed temp occ card, contr has a few items left, switch in computer room, a few ballasts, panel schedules, couple switch cover, low voltage bushings
|
ELE05-04125
| Temporary Service | 11/23/2005 | 11/23/2005 | 11/23/2005 12:04:40 PM | P | PASS |
|
|
vivian; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corr made, t/s o/h n ok
|
ELE05-04246
| Rough-In Permanent Service | 11/22/2005 | 11/23/2005 | 11/23/2005 10:19:59 AM | A | PASS |
|
|
Charlie; Phone #: ###-#### Internet Inspection Request from: Melyne Davis ric ok, p/s u/g n ok
|
ELE05-03534
| Electrical Rough-In | 11/23/2005 | 11/23/2005 | 11/23/2005 9:29:17 AM | P | PASS |
|
|
Ceiling inspection; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson corrections made, clg cover ok
|
ELE05-04010
| Electrical Rough-In | 11/23/2005 | 11/23/2005 | 11/23/2005 9:10:52 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/23/2005 at 7:29:25 AM. Contact: ###-####. ric ok, corrections made
|
ELE05-03097
| Final | 11/22/2005 | 11/23/2005 | 11/23/2005 8:13:52 AM | A | PASS |
|
|
daryl; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final
|
ELE05-03924
| Electrical Rough-In | 11/22/2005 | 11/23/2005 | 11/23/2005 8:12:33 AM | A | PASS |
|
|
WET NICHE LIGHTING ON A SWIMMING POOL; Phone #: ###-#### Internet Inspection Request from: Barry Kendall potting ok
|