Inspections for the day of: Wednesday, November 23, 2005.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-01831 FIRE-Final Inspection11/23/200511/23/200511/23/2005 5:40:26 PMPCANC
###-#### - joel No time available for this inspection today, to be rescheduled per conversation.
FIR05-00718 INSP-Final Inspection11/22/200511/23/200511/23/2005 5:38:30 PMAFAIL
Plans still not available on site for review or inspection.
BLD04-02970 FIRE-Final Inspection11/22/200511/23/200511/23/2005 5:37:34 PMACANC
No time available for this inspection today, to be rescheduled per agreement.
BLD05-00521 FIRE-Final Inspection11/23/200511/23/200511/23/2005 5:35:37 PMPCANC
No time available for this inspection today, the related fire alarm and sprinkler permits must be finaled prior to life safety approval.
MIS05-00195 FIR-Final11/23/200511/23/200511/23/2005 5:33:36 PMPCANC
To be scheduled for 11/25
FIR05-00742 INSP-Final Inspection11/23/200511/23/200511/23/2005 4:23:58 PMPCANC
No time available for this inspection today.
FIR05-00741 INSP-Final Inspection11/23/200511/23/200511/23/2005 4:23:07 PMPPART
This inspection already completed, see am entry.
FIR05-00666 INSP-Alarm Testing11/22/200511/23/200511/23/2005 4:20:12 PMPPART
Three notification devices were corrected while on site, duct detectors tested okay, fire alarm tested acceptable, final pending shell permit final.
FIR05-00076 INSP-Alarm Testing11/22/200511/23/200511/23/2005 4:17:25 PMPPART
The north elevator alarm devices tested okay.
BLD05-02432 FIRE-Final Inspection11/22/200511/23/200511/23/2005 4:15:45 PMPPART
Items on the correction notice issued 11/22 have been completed, final pending alarm resubmittals for device address changes and shell permit finals for alarm and sprinkler.
FIR05-00576 INSP-Final Inspection11/23/200511/23/200511/23/2005 2:08:48 PMPCANC
This is my #. Please call me 20-30 minutes prior toy your arrival. Thanks, Grant; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
FIR05-00577 INSP-Final Inspection11/22/200511/23/200511/23/2005 12:52:29 PMAFAIL
The rough-in inspection failed, alarms are not connected, ceiling tile is not installed, the hydrostatic test failed due to a leaking #1 shutoff valve at the riser backflow.
FIR05-00577 INSP-Sprinkler Rough-in/Hydro11/22/200511/23/200511/23/2005 12:50:32 PMAFAIL
See approved plans for areas in the office and sales floor for defficiencies including head location, temperatures, hangers, taped or painted heads, also need verification of type of plywood installed above the exterior canopy, not a complete inspection at this time.
BLD05-01956 FIRE-Final Inspection11/22/200511/23/200511/23/2005 11:04:14 AMAPASS
c/n items have been completed, life safety passed.
MIS05-00193 FIR-Final11/22/200511/23/200511/23/2005 10:43:48 AMAPASS
Fire life safety is acceptable. Note, NO storage or occupancy use is allowed in the basement mechanical room.
FIR05-00796 INSP-Final Inspection11/22/200511/23/200511/23/2005 9:18:45 AMAPASS
Hood suppression system operated correctly under test conditions, the K class extinguisher was relocated to a proper distance from the hood.
BLD05-00458 FIRE-Final Inspection11/22/200511/23/200511/23/2005 9:16:33 AMAPART
Correction notice items have been completed, fire life safety is acceptable pending testing of the duct smoke detectors for completion of the alarm permit inspection.
BLD05-02476 FIRE-Final Inspection11/23/200511/23/200511/23/2005 8:22:44 AMAPART
Fire life safety is acceptable, final pending shell permit finals for alarm and sprinkler.
FIR05-00741 INSP-Final Inspection11/23/200511/23/200511/23/2005 12:00:00 AMAPART
Fire sprinkler passed inspection, final pending shell sprinkler final.
BLD05-00521 FIRE-Final Inspection11/22/200511/23/200511/23/2005 12:00:00 AMACANC
bill ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie///cancelled per Bill w/Cafco will call to reschedule //11/22/05 LEG 4:28pm
BLD05-00458 FIRE-Final Inspection11/22/200511/23/200511/22/2005 7:18:20 PMACANC
Duplicate inspection already scheduled.
FIR05-00075 INSP-Alarm Testing11/22/200511/23/200511/22/2005 2:39:25 PMPCANC
Scheduled by a contractor via Hello! on 11/22/2005 at 2:37:38 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Nov 22 2005 2:39PM.