BLD05-01831
| FIRE-Final Inspection | 11/23/2005 | 11/23/2005 | 11/23/2005 5:40:26 PM | P | CANC |
|
|
###-#### - joel No time available for this inspection today, to be rescheduled per conversation.
|
FIR05-00718
| INSP-Final Inspection | 11/22/2005 | 11/23/2005 | 11/23/2005 5:38:30 PM | A | FAIL |
|
|
Plans still not available on site for review or inspection.
|
BLD04-02970
| FIRE-Final Inspection | 11/22/2005 | 11/23/2005 | 11/23/2005 5:37:34 PM | A | CANC |
|
|
No time available for this inspection today, to be rescheduled per agreement.
|
BLD05-00521
| FIRE-Final Inspection | 11/23/2005 | 11/23/2005 | 11/23/2005 5:35:37 PM | P | CANC |
|
|
No time available for this inspection today, the related fire alarm and sprinkler permits must be finaled prior to life safety approval.
|
MIS05-00195
| FIR-Final | 11/23/2005 | 11/23/2005 | 11/23/2005 5:33:36 PM | P | CANC |
|
|
To be scheduled for 11/25
|
FIR05-00742
| INSP-Final Inspection | 11/23/2005 | 11/23/2005 | 11/23/2005 4:23:58 PM | P | CANC |
|
|
No time available for this inspection today.
|
FIR05-00741
| INSP-Final Inspection | 11/23/2005 | 11/23/2005 | 11/23/2005 4:23:07 PM | P | PART |
|
|
This inspection already completed, see am entry.
|
FIR05-00666
| INSP-Alarm Testing | 11/22/2005 | 11/23/2005 | 11/23/2005 4:20:12 PM | P | PART |
|
|
Three notification devices were corrected while on site, duct detectors tested okay, fire alarm tested acceptable, final pending shell permit final.
|
FIR05-00076
| INSP-Alarm Testing | 11/22/2005 | 11/23/2005 | 11/23/2005 4:17:25 PM | P | PART |
|
|
The north elevator alarm devices tested okay.
|
BLD05-02432
| FIRE-Final Inspection | 11/22/2005 | 11/23/2005 | 11/23/2005 4:15:45 PM | P | PART |
|
|
Items on the correction notice issued 11/22 have been completed, final pending alarm resubmittals for device address changes and shell permit finals for alarm and sprinkler.
|
FIR05-00576
| INSP-Final Inspection | 11/23/2005 | 11/23/2005 | 11/23/2005 2:08:48 PM | P | CANC |
|
|
This is my #. Please call me 20-30 minutes prior toy your arrival. Thanks, Grant; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
|
FIR05-00577
| INSP-Final Inspection | 11/22/2005 | 11/23/2005 | 11/23/2005 12:52:29 PM | A | FAIL |
|
|
The rough-in inspection failed, alarms are not connected, ceiling tile is not installed, the hydrostatic test failed due to a leaking #1 shutoff valve at the riser backflow.
|
FIR05-00577
| INSP-Sprinkler Rough-in/Hydro | 11/22/2005 | 11/23/2005 | 11/23/2005 12:50:32 PM | A | FAIL |
|
|
See approved plans for areas in the office and sales floor for defficiencies including head location, temperatures, hangers, taped or painted heads, also need verification of type of plywood installed above the exterior canopy, not a complete inspection at this time.
|
BLD05-01956
| FIRE-Final Inspection | 11/22/2005 | 11/23/2005 | 11/23/2005 11:04:14 AM | A | PASS |
|
|
c/n items have been completed, life safety passed.
|
MIS05-00193
| FIR-Final | 11/22/2005 | 11/23/2005 | 11/23/2005 10:43:48 AM | A | PASS |
|
|
Fire life safety is acceptable. Note, NO storage or occupancy use is allowed in the basement mechanical room.
|
FIR05-00796
| INSP-Final Inspection | 11/22/2005 | 11/23/2005 | 11/23/2005 9:18:45 AM | A | PASS |
|
|
Hood suppression system operated correctly under test conditions, the K class extinguisher was relocated to a proper distance from the hood.
|
BLD05-00458
| FIRE-Final Inspection | 11/22/2005 | 11/23/2005 | 11/23/2005 9:16:33 AM | A | PART |
|
|
Correction notice items have been completed, fire life safety is acceptable pending testing of the duct smoke detectors for completion of the alarm permit inspection.
|
BLD05-02476
| FIRE-Final Inspection | 11/23/2005 | 11/23/2005 | 11/23/2005 8:22:44 AM | A | PART |
|
|
Fire life safety is acceptable, final pending shell permit finals for alarm and sprinkler.
|
FIR05-00741
| INSP-Final Inspection | 11/23/2005 | 11/23/2005 | 11/23/2005 12:00:00 AM | A | PART |
|
|
Fire sprinkler passed inspection, final pending shell sprinkler final.
|
BLD05-00521
| FIRE-Final Inspection | 11/22/2005 | 11/23/2005 | 11/23/2005 12:00:00 AM | A | CANC |
|
|
bill ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie///cancelled per Bill w/Cafco will call to reschedule //11/22/05 LEG 4:28pm
|
BLD05-00458
| FIRE-Final Inspection | 11/22/2005 | 11/23/2005 | 11/22/2005 7:18:20 PM | A | CANC |
|
|
Duplicate inspection already scheduled.
|
FIR05-00075
| INSP-Alarm Testing | 11/22/2005 | 11/23/2005 | 11/22/2005 2:39:25 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 11/22/2005 at 2:37:38 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Nov 22 2005 2:39PM.
|