Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00518 INSP-Conference11/13/200911/16/2009 P 
KEN Phone #: ###-#### (Follow up with Jerry McAdams)
FIR09-00662 INSP-Final Inspection11/23/200911/23/200911/23/2009 4:08:24 PMPPASS
Permit finaled
BLD09-01682 FIRE-Final Inspection11/20/200911/23/200911/23/2009 2:49:25 PMAFAIL
The owner received the wrong set of permit/drawings from city hall so no inspection was performed. I noted that the two exit sign/emergency lights did not function and the existing fire extinguisher was not mounted and it did not have a current inspection tag.
BLD09-00846 FIRE-Final Inspection11/23/200911/23/200911/23/2009 2:23:30 PMPFAIL
Provide the modified occupant load sign, provide exit signs/emergency lights as discussed and shown on the city approved plans and provide one additional fire extinguisher at the north end of the new dining room.
FIR09-00600 INSP-Sprinkler Rough-in/Hydro11/20/200911/23/200911/23/2009 1:36:11 PMAPASS
The overhead hydro test passed and the branchline restraints have now been added.