FIR09-00518
| INSP-Conference | 11/13/2009 | 11/16/2009 | | P | |
|
|
KEN Phone #: ###-#### (Follow up with Jerry McAdams)
|
FIR09-00662
| INSP-Final Inspection | 11/23/2009 | 11/23/2009 | 11/23/2009 4:08:24 PM | P | PASS |
|
|
Permit finaled
|
BLD09-01682
| FIRE-Final Inspection | 11/20/2009 | 11/23/2009 | 11/23/2009 2:49:25 PM | A | FAIL |
|
|
The owner received the wrong set of permit/drawings from city hall so no inspection was performed. I noted that the two exit sign/emergency lights did not function and the existing fire extinguisher was not mounted and it did not have a current inspection tag.
|
BLD09-00846
| FIRE-Final Inspection | 11/23/2009 | 11/23/2009 | 11/23/2009 2:23:30 PM | P | FAIL |
|
|
Provide the modified occupant load sign, provide exit signs/emergency lights as discussed and shown on the city approved plans and provide one additional fire extinguisher at the north end of the new dining room.
|
FIR09-00600
| INSP-Sprinkler Rough-in/Hydro | 11/20/2009 | 11/23/2009 | 11/23/2009 1:36:11 PM | A | PASS |
|
|
The overhead hydro test passed and the branchline restraints have now been added.
|