Inspections for the day of: Wednesday, November 23, 2011.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-02607 FIRE-Conference11/23/201111/23/201111/23/2011 4:32:18 PMPPART
Contact Doug regarding building fire alarm
FIR11-00301 INSP-Sprinkler Rough-in/Hydro11/22/201111/23/201111/23/2011 4:29:36 PMPNR
Please contact Jeremiah prior to arrival. Phone #: ###-#### >> Inspection requested via web by Alicia Pauley NOTE: **Area requested for inspection is not included in the scope of this permit (FIR11-00301 covers system 8 sub-fab). Contractor intended an overhead inspection for system 4 photo bay for which permit FIR11-00524 is not yet approved or issued at this time. Noted system 4 mains and branchlines already installed. No inspection performed due to permit status and lack of approved drawings.**
FIR11-00496 INSP-Sprinkler Rough-in11/22/201111/23/201111/23/2011 4:08:17 PMAPART
Verified retainers at beam clamps in the parking garage, rough-in at units 101 thru 108 first floor okayed. See dated plan annotations.
FIR11-00528 INSP-Conference11/23/201111/23/201111/23/2011 1:54:52 PMADONE
On site meeting with contractor and mechanical inspectors regarding missing smoke detection at existing air handler units and conditions per IMC 2009 sec. 606.
FIR11-00627 INSP-Sprinkler Rough-in11/23/201111/23/201111/23/2011 12:00:00 AMPCANC
ken Phone #: ###-####
FIR11-00627 INSP-Final Inspection11/23/201111/23/201111/23/2011 12:00:00 AMPCANC
ken Phone #: ###-####