Inspections for the day of: Monday, November 23, 2015.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-03796 Permanent Service11/23/201511/23/201511/23/2015 2:53:20 PMPFAIL
New Meter Inspection Phone #: ###-#### Inspection requested via web by Celinda Winters 110.24- Available fault current shall be posted with date calculated prior to permenant service inspection.
358.22- Conductor fill shall ot exceed that permitted by the percentage specified in table 1 chapter 9. .122" max .185" installed. 3/4" EMT conduit minimum. 60% fill applies due to 16" length. Conduit ok
ELE15-03799 Rough-In Permanent Service11/23/201511/23/201511/23/2015 2:33:39 PMPPASS
Phone #: ###-#### Inspection requested via web by ron spen cer
Service energized prior to inspection. Called Idaho Power and rep was called to trouble shoot issue, due to super intendant being difficult decided to push power to meter base. Informed Idaho Power and electrical contractor if power connected again prior to inspection a stop work order will be issued until resolved. Rough in ok cover p/s u/g n ok
ELE15-03396 Electrical Rough-In11/20/201511/23/201511/23/2015 1:50:21 PMPPASS
We need an underground inspection. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Under slab (C) rough in ok cover
ELE15-03436 Rough-In Permanent Service11/23/201511/23/201511/23/2015 12:52:23 PMPFAIL
Phone #: ###-#### Inspection requested via web by Brandon Hillman
110.12- Check repair or replace damaged NM cable run to garage receptacles.
210.52(B)(1)- Dining area receptacle outlets shall be wired with 20 amp 120 volt small appliance circuit.
250.8- Main bonding screw shall be installed in panel for permenant service.
300.4- Speaker wire installed in family room where it may be damaged by drywall installation.
334.30- NM cable shall be secured with in 12" of master vanity light box.
ELE15-03777 Temporary Service11/20/201511/23/201511/23/2015 11:42:53 AMPFAIL
Phone #: ###-#### Inspection requested via web by David Nelson Correction not complete
ELE15-03791 Electrical Rough-In11/20/201511/23/201511/23/2015 11:24:36 AMACANC
Phone #: ###-#### Inspection requested via web by David Nelson Duplicate request see RI/PS
ELE15-03791 Rough-In Permanent Service11/20/201511/23/201511/23/2015 11:23:58 AMAPASS
Phone #: ###-#### Inspection requested via web by David Nelson Rough in ok cover p/s u/g n ok
ELE15-03024 Final11/20/201511/23/201511/23/2015 10:54:39 AMAPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov
Final ok
ELE15-03058 Final11/20/201511/23/201511/23/2015 10:54:10 AMAPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov
Final ok
ELE15-03796 Final11/23/201511/23/201511/23/2015 10:17:22 AMACANC
New Meter Inspection Phone #: ###-#### Inspection requested via web by Celinda Winters Needed permenant service inspection.
ELE15-03143 Final11/20/201511/23/201511/23/2015 9:06:50 AMAPASS
Garage code is 0500 Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok