ELE15-03796
| Permanent Service | 11/23/2015 | 11/23/2015 | 11/23/2015 2:53:20 PM | P | FAIL |
|
|
New Meter Inspection Phone #: ###-#### Inspection requested via web by Celinda Winters 110.24- Available fault current shall be posted with date calculated prior to permenant service inspection. 358.22- Conductor fill shall ot exceed that permitted by the percentage specified in table 1 chapter 9. .122" max .185" installed. 3/4" EMT conduit minimum. 60% fill applies due to 16" length. Conduit ok
|
ELE15-03799
| Rough-In Permanent Service | 11/23/2015 | 11/23/2015 | 11/23/2015 2:33:39 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by ron spen cer Service energized prior to inspection. Called Idaho Power and rep was called to trouble shoot issue, due to super intendant being difficult decided to push power to meter base. Informed Idaho Power and electrical contractor if power connected again prior to inspection a stop work order will be issued until resolved. Rough in ok cover p/s u/g n ok
|
ELE15-03396
| Electrical Rough-In | 11/20/2015 | 11/23/2015 | 11/23/2015 1:50:21 PM | P | PASS |
|
|
We need an underground inspection. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Under slab (C) rough in ok cover
|
ELE15-03436
| Rough-In Permanent Service | 11/23/2015 | 11/23/2015 | 11/23/2015 12:52:23 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Brandon Hillman 110.12- Check repair or replace damaged NM cable run to garage receptacles. 210.52(B)(1)- Dining area receptacle outlets shall be wired with 20 amp 120 volt small appliance circuit. 250.8- Main bonding screw shall be installed in panel for permenant service. 300.4- Speaker wire installed in family room where it may be damaged by drywall installation. 334.30- NM cable shall be secured with in 12" of master vanity light box.
|
ELE15-03777
| Temporary Service | 11/20/2015 | 11/23/2015 | 11/23/2015 11:42:53 AM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by David Nelson Correction not complete
|
ELE15-03791
| Electrical Rough-In | 11/20/2015 | 11/23/2015 | 11/23/2015 11:24:36 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by David Nelson Duplicate request see RI/PS
|
ELE15-03791
| Rough-In Permanent Service | 11/20/2015 | 11/23/2015 | 11/23/2015 11:23:58 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by David Nelson Rough in ok cover p/s u/g n ok
|
ELE15-03024
| Final | 11/20/2015 | 11/23/2015 | 11/23/2015 10:54:39 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Final ok
|
ELE15-03058
| Final | 11/20/2015 | 11/23/2015 | 11/23/2015 10:54:10 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Final ok
|
ELE15-03796
| Final | 11/23/2015 | 11/23/2015 | 11/23/2015 10:17:22 AM | A | CANC |
|
|
New Meter Inspection Phone #: ###-#### Inspection requested via web by Celinda Winters Needed permenant service inspection.
|
ELE15-03143
| Final | 11/20/2015 | 11/23/2015 | 11/23/2015 9:06:50 AM | A | PASS |
|
|
Garage code is 0500 Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok
|