ELE16-03822
| Electrical Rough-In | 11/23/2016 | 11/23/2016 | 11/23/2016 1:34:23 PM | P | PASS |
|
|
Rough in for the back section of the tenant space Phone #: ###-#### Inspection requested via web by Steve Craig Back bathrooms and shower plus misc walls rough in ok cover
|
ELE16-03157
| Final | 11/22/2016 | 11/23/2016 | 11/23/2016 12:54:11 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Final ok
|
ELE16-02391
| Final | 11/22/2016 | 11/23/2016 | 11/23/2016 10:58:26 AM | A | PASS |
|
|
brandon Phone #: ###-#### Final ok
|
ELE16-02557
| Final | 11/23/2016 | 11/23/2016 | 11/23/2016 10:57:56 AM | P | PASS |
|
|
2nd permit exists for same areas. ELE16-02391 requested final so doing this permit as well. Final ok
|
ELE16-03736
| Electrical Rough-In | 11/22/2016 | 11/23/2016 | 11/23/2016 10:27:25 AM | A | FAIL |
|
|
Most of remodeling was exsisting. I only added one circuit. And moved lights and switches. All my work is marked with blue tape. Phone #: ###-#### Inspection requested via web by Brannon Brown Work exists that is not covered by this permit. Asked contractor if he did work and he denied responcibility. New walls in bed, bath, kitchen. New range hood, bath fan. New plumbing in bath, shower, kitchen area Stop work order posted.
|
MIS16-00373
| ELE-Conference | 11/23/2016 | 11/23/2016 | 11/23/2016 10:26:37 AM | P | DONE |
|
|
Someone shall have a permit that covers wiring dated 2012. Once done shall cal in rough in inspection. If existing grounding type receptacles on ungrounded circuits they shall have GFCI protection or changed to ungrounded type receptacles.
|