ELE07-00275
| ELE-Aging Inspection | 11/24/2008 | 11/24/2008 | 12/1/2008 10:10:23 AM | | DONE |
|
|
contractor to call for inspection, called, left message, no esc this project
|
ELE08-03108
| Conference | 11/24/2008 | 11/24/2008 | 11/24/2008 4:14:56 PM | P | DONE |
|
|
Brian Phone #: ###-#### talked about service, grounding, relocating, calling for inspection, clean-up of old violations
|
ESC08-00893
| General Inspection | 11/24/2008 | 11/24/2008 | 11/24/2008 3:45:41 PM | P | PASS |
|
|
looked ok
|
ESC08-00532
| General Inspection | 11/24/2008 | 11/24/2008 | 11/24/2008 3:44:55 PM | P | PASS |
|
|
looked ok
|
ESC08-00912
| General Inspection | 11/24/2008 | 11/24/2008 | 11/24/2008 3:44:03 PM | P | PASS |
|
|
looked ok
|
ESC08-00817
| General Inspection | 11/24/2008 | 11/24/2008 | 11/24/2008 3:41:29 PM | P | PASS |
|
|
looked ok
|
ESC08-00884
| General Inspection | 11/24/2008 | 11/24/2008 | 11/24/2008 3:40:29 PM | P | PASS |
|
|
looked ok
|
ESC08-00959
| General Inspection | 11/24/2008 | 11/24/2008 | 11/24/2008 3:39:24 PM | A | PASS |
|
|
looked ok
|
ESC08-00951
| General Inspection | 11/24/2008 | 11/24/2008 | 11/24/2008 3:37:51 PM | A | PASS |
|
|
looked ok
|
ELE08-03000
| Final | 11/23/2008 | 11/24/2008 | 11/24/2008 3:36:04 PM | P | PASS |
|
|
PLEASE CALL BRAD WITH YOUR SCHEDULE FOR ARRIVAL SO HE CAN MEET YOU THANKS Phone #: ###-#### Internet Inspection Request from: Brad Baker ok to final, signed occupancy card, no esc this project
|
ELE08-02977
| Electrical Rough-In | 11/24/2008 | 11/24/2008 | 11/24/2008 2:51:17 PM | P | PASS |
|
|
richard Phone #: ###-#### Note; please call 1/2 hr prior to inspection ric ok walls and ceiling in shop only
|
ELE08-03102
| Permanent Service | 11/24/2008 | 11/24/2008 | 11/24/2008 2:13:22 PM | P | NR |
|
|
mike Phone #: ###-#### called, not done, no literature available, will recall, fee due
|
ELE08-03107
| Rough-In Permanent Service | 11/24/2008 | 11/24/2008 | 11/24/2008 1:27:48 PM | P | CANC |
|
|
darren Phone #: ###-#### wrong type request see p/s
|
ELE08-03107
| Permanent Service | 11/24/2008 | 11/24/2008 | 11/24/2008 12:59:46 PM | P | PASS |
|
|
darren Phone #: ###-#### p/s u/g n ok
|
ELE08-03107
| Electrical Rough-In | 11/24/2008 | 11/24/2008 | 11/24/2008 12:52:04 PM | P | FAIL |
|
|
darren Phone #: ###-#### called contractor, left correction notice,NEC 334.30 nm cable shall not be stapled on edge, and shall be stapled within 12" of panel, 210.52(H) hallway over 10' shall have receptacle outlet
|
ELE08-02905
| Rough-In Permanent Service | 11/24/2008 | 11/24/2008 | 11/24/2008 12:34:45 PM | P | NR |
|
|
Please provide rough-in partial inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean called at entrance, not ready for pm inspection, fee due
|
ELE08-03098
| Electrical Rough-In | 11/21/2008 | 11/24/2008 | 11/24/2008 10:35:28 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Bob Glenn called contractor left survey, NEC 210.70(A)(2)(b) shall provide switched lighting outlet at outdoor entrance at grade level. Vehicle door shall be considered entrance, 320.23(A) cable shall be protected within 6' of attic access ric ok, no power provisions until later
|
ELE08-03026
| Electrical Rough-In | 11/21/2008 | 11/24/2008 | 11/24/2008 9:59:52 AM | A | PASS |
|
|
chris - walls and ceiling Phone #: ###-#### walls and hard lids only ok to cover
|
ELE08-03099
| Rough-In Permanent Service | 11/21/2008 | 11/24/2008 | 11/24/2008 9:23:07 AM | A | PASS |
|
|
Lock box combo 1290. Any questions or concerns call Clay at ###-####. Thanks. Phone #: ###-#### Internet Inspection Request from: Clay Morgan ric ok, p/s, exst meter pak, rec, ok, no esc this project
|
ELE08-03096
| Temporary Service | 11/21/2008 | 11/24/2008 | 11/24/2008 8:26:24 AM | A | FAIL |
|
|
Hi Bob, The temp. power pole is located at the back of the property, if you have any questions please call. Thx. Wayne Phone #: ###-#### Internet Inspection Request from: Wayne Craig called left correction notice, NEC 250.24(A) gec shall connect to grounded service conductor, 250.53(G) upper end of electrode shall be flush with or below ground unless protected from physical damage, fee due, no esc this project
|
ELE08-03096
| Final | 11/21/2008 | 11/24/2008 | 11/21/2008 10:55:59 AM | A | CANC |
|
|
Hi Bob,
I need an inspection on the temp. power pole. The temp. power pole is located in the back of the property, if you have any questions please call.
Thx. Wayne Phone #: ###-#### Internet Inspection Request from: Wayne Craig Inspection cancelled from web by: Wayne Craig
|