Inspections for the day of: Wednesday, November 24, 2010.
Number of inspections: 9
Percentage of inspections complete: 89 %
Percentage of inspections not complete: 11 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00555 INSP-Final Inspection11/17/201011/18/2010 A 
This inspection will be in the fab. Contact Dan Tuskey at ###-#### for access. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
FIR10-00578 INSP-Final Inspection11/22/201011/24/201011/26/2010 7:36:58 AMPFAIL
Need to relocate the manual pull as discussed, power at one half of the hood appliances did not shut down upon system activation.
BLD10-01041 FIRE-Final Inspection11/23/201011/24/201011/24/2010 2:00:13 PMPFAIL
Items noted include; post one fire extinguisher at the basement level, provide approved door hardware at the first floor east exit door, remove the chevron at exit sign in the hall for dual direction per plan, install closure and seal at the rated basement door, remove the drawbridge and associated equipment at the basement stairway in non-compliance with egress requirements per IFC 2006.
FIR10-00570 INSP-Final Inspection11/22/201011/24/201011/24/2010 1:46:08 PMAPASS
Functional testing passed. Fire alarm permit final approved.
FIR10-00568 INSP-Final Inspection11/23/201011/24/201011/24/2010 1:44:53 PMAPART
Fire sprinkler work passed rough-in inspection.
FIR06-00240 FIR-Aging Inspection11/24/201011/24/201011/24/2010 11:46:08 AM PEND
Ref. activity notes
BLD10-02614 FIRE-Final Inspection11/23/201011/24/201011/24/2010 11:44:23 AMAFAIL
Existing portable fire extinguishers throughout both the first floor and basement are overdue annual certification. Provide a current inspection for the basement fire sprinkler system. Discussed schedule for occupancy.
BLD10-01976 FIRE-Final Inspection11/22/201011/24/201011/24/2010 11:39:54 AMAPASS
Fire life safety completed acceptable. Inspection passed.
FIR10-00574 INSP-Final Inspection11/23/201011/24/201011/24/2010 11:39:00 AMAPASS
Fire sprinkler permit work passed final inspection.