FIR10-00555
| INSP-Final Inspection | 11/17/2010 | 11/18/2010 | | A | |
|
|
This inspection will be in the fab. Contact Dan Tuskey at ###-#### for access. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
|
FIR10-00578
| INSP-Final Inspection | 11/22/2010 | 11/24/2010 | 11/26/2010 7:36:58 AM | P | FAIL |
|
|
Need to relocate the manual pull as discussed, power at one half of the hood appliances did not shut down upon system activation.
|
BLD10-01041
| FIRE-Final Inspection | 11/23/2010 | 11/24/2010 | 11/24/2010 2:00:13 PM | P | FAIL |
|
|
Items noted include; post one fire extinguisher at the basement level, provide approved door hardware at the first floor east exit door, remove the chevron at exit sign in the hall for dual direction per plan, install closure and seal at the rated basement door, remove the drawbridge and associated equipment at the basement stairway in non-compliance with egress requirements per IFC 2006.
|
FIR10-00570
| INSP-Final Inspection | 11/22/2010 | 11/24/2010 | 11/24/2010 1:46:08 PM | A | PASS |
|
|
Functional testing passed. Fire alarm permit final approved.
|
FIR10-00568
| INSP-Final Inspection | 11/23/2010 | 11/24/2010 | 11/24/2010 1:44:53 PM | A | PART |
|
|
Fire sprinkler work passed rough-in inspection.
|
FIR06-00240
| FIR-Aging Inspection | 11/24/2010 | 11/24/2010 | 11/24/2010 11:46:08 AM | | PEND |
|
|
Ref. activity notes
|
BLD10-02614
| FIRE-Final Inspection | 11/23/2010 | 11/24/2010 | 11/24/2010 11:44:23 AM | A | FAIL |
|
|
Existing portable fire extinguishers throughout both the first floor and basement are overdue annual certification. Provide a current inspection for the basement fire sprinkler system. Discussed schedule for occupancy.
|
BLD10-01976
| FIRE-Final Inspection | 11/22/2010 | 11/24/2010 | 11/24/2010 11:39:54 AM | A | PASS |
|
|
Fire life safety completed acceptable. Inspection passed.
|
FIR10-00574
| INSP-Final Inspection | 11/23/2010 | 11/24/2010 | 11/24/2010 11:39:00 AM | A | PASS |
|
|
Fire sprinkler permit work passed final inspection.
|