Inspections for the day of: Monday, November 24, 2014.
Number of inspections: 12
Percentage of inspections complete: 92 %
Percentage of inspections not complete: 8 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00461 INSP-Sprinkler Rough-in/Hydro11/17/201411/18/2014 A 
Inspect fire sprinkler heat trace in basement. Call Jon Novak. Phone #: ###-#### >> Inspection requested via web by Tom Betty
FIR14-00612 INSP-Sprinkler Rough-in/Hydro11/24/201411/24/201411/24/2014 5:48:38 PMPPART
Overhead hydrostatic test of the new dry system completed satisfactory.
BLD14-01038 FIRE-Final Inspection11/21/201411/24/201411/24/2014 5:47:03 PMAPASS
Life safety passed provided door hardware at the second exit is revised to meet IBC requirements. To be done prior to structural final.
BLD14-01876 FIRE-Final Inspection11/24/201411/24/201411/24/2014 2:39:05 PMPPASS
Scope of work completed. Fire life safety inspection passed.
BLD14-01381 FIRE-Final Inspection11/24/201411/24/201411/24/2014 2:38:08 PMPPASS
Re-inspection completed. Vanilla shell fire life safety passed.
BLD14-01381 FIRE-Final Inspection11/21/201411/24/201411/24/2014 1:44:09 PMAFAIL
Need to provide plans for verification of work completed.
BLD14-01876 FIRE-Final Inspection11/21/201411/24/201411/24/2014 1:43:06 PMANH
Missing access, plans and permit documents on site.
FIR14-00333 INSP-Final Inspection11/24/201411/24/201411/24/2014 1:39:13 PMAPART
Notification appliances at the new lab passed inspection and testing. Permit final pending program changes for new duct detectors.
FIR14-00319 INSP-Final Inspection11/21/201411/24/201411/24/2014 1:35:53 PMAPASS
Scope of fire sprinkler work at the new lab completed. Mains and branchlines extending to the next phase are installed, however drop ceilings and pendent heads are not yet provided.
FIR14-00391 INSP-Final Inspection11/24/201411/24/201411/24/2014 1:32:49 PMAPASS
Scope of fire alarm work passed functional testing and inspection. Permit finaled.
BLD14-01506 FIRE-Final Inspection11/21/201411/24/201411/24/2014 1:30:56 PMAPART
Final pending project related fire alarm permit work and missing exit sign per plan review red-line annotations.
FIR14-00612 INSP-Sprinkler Rough-in/Hydro11/21/201411/24/201411/24/2014 1:28:29 PMAPART
Completed overhead hydrostatic test of the new wet system piping and inspection for cover at grid ceilings in the new multipurpose room and adjacent corridor north end.