Inspections for the day of: Monday, November 24, 2014.
Number of inspections: 10
Percentage of inspections complete: 90 %
Percentage of inspections not complete: 10 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD14-03366 FIRE-Final Inspection11/17/201411/18/2014 P 
Elise// please call 45 min prior Phone #: ###-####
BLD14-03061 FIRE-Final Inspection11/21/201411/24/201411/24/2014 3:39:36 PMPPASS
Life safety passed. Per Tim Woodard exit signs are not required. Possible issue with deadbolt on sliding door.
FIR14-00423 INSP-Sprinkler Rough-in11/24/201411/24/201411/24/2014 3:05:18 PMPFAIL
Tenting inspection failed. Provide re-inspection prior to cover of pipe.
FIR13-00697 INSP-Sprinkler Rough-in/Hydro11/20/201411/24/201411/24/2014 2:31:26 PMAPASS
Hydro test of the pre-action system passed
FIR14-00789 INSP-Final Inspection11/21/201411/24/201411/24/2014 12:12:50 PMAPASS
Permit finaled
FIR14-00854 INSP-Final Inspection11/23/201411/24/201411/24/2014 12:12:31 PMAFAIL
Strobes in Pizza and Customer Services areas have not been set for the correct candella which makes them currectly overspaced. Work shown near/in the Bakery has not been performed and if installed as per the plans will still be defiecient as discussed. Contractor shall contact plan review to verify whether as-builts will be adequate or if plan modifications will be required.
BLD14-03253 FIRE-Final Inspection11/21/201411/24/201411/24/2014 11:56:39 AMAPASS
life safety passed
FIR14-00796 INSP-Final Inspection11/21/201411/24/201411/24/2014 10:01:42 AMAPASS
Permit finaled
FIR14-00797 INSP-Final Inspection11/21/201411/24/201411/24/2014 10:01:19 AMAPASS
Permit finaled
BLD14-02414 FIRE-Final Inspection11/21/201411/24/201411/24/2014 10:00:50 AMAFAIL
Remove thumbturn dead bolt from main exit (keyed ok), provide sticker at main exit, mount fire extinguisher as discussed for the upper level, provide re-inspection for fire extinguisher in lower level and repair exit sign/emergency lights in lower level. Per Carl door hardware does not need addressed in the lower level since it is to remain un-occupied.