BLD09-00510
| FIRE-Sprinkler Rough-in | 11/25/2009 | 11/25/2009 | 11/27/2009 10:54:45 AM | P | PART |
|
|
Okayed overhead cover for fire sprinkler install-see green tag on site.
|
FIR09-00542
| INSP-Final Inspection | 11/12/2009 | 11/25/2009 | 11/25/2009 1:51:21 PM | A | PASS |
|
|
Fire alarm permit work okayed for final status, inspection passed.
|
FIR09-00553
| INSP-Final Inspection | 11/12/2009 | 11/25/2009 | 11/25/2009 1:50:11 PM | A | PASS |
|
|
Site testing passed, fire alarm permit final approved.
|
FIR09-00554
| INSP-Final Inspection | 11/12/2009 | 11/25/2009 | 11/25/2009 1:48:51 PM | A | PASS |
|
|
Fire alarm permit finaled.
|
FIR09-00663
| INSP-Final Inspection | 11/24/2009 | 11/25/2009 | 11/25/2009 12:15:47 PM | A | FAIL |
|
|
Activation of the suppression system failed to shunt power to the electrical outlets under the hood, also need to provide a junction box outside the agent cabinet for wiring connections. Manual pull has not been tested.
|
BLD09-01283
| FIRE-Final Inspection | 11/24/2009 | 11/25/2009 | 11/25/2009 12:10:30 PM | A | NR |
|
|
Project related fire alarm permit has not been requested for inspection and must be finaled prior to building fire life safety signature.
|
BLD09-01822
| FIRE-Final Inspection | 11/25/2009 | 11/25/2009 | 11/25/2009 12:08:46 PM | A | PASS |
|
|
Life safety inspection passed.
|
BLD09-01822
| FIRE-Supply Line Hydro | 11/24/2009 | 11/25/2009 | 11/25/2009 12:08:15 PM | A | PART |
|
|
NOTE: Inspection request type is incorrect, intended for life safety review/approval.
|
FIR09-00670
| INSP-Sprinkler Rough-in | 11/24/2009 | 11/25/2009 | 11/25/2009 12:04:43 PM | A | FAIL |
|
|
Noted overspaced heads at three offices, see red lines marked with today's date for locations. Remainder of permit work is okay for cover at the drop ceilings.
|
BLD09-01937
| FIRE-Final Inspection | 11/24/2009 | 11/25/2009 | 11/25/2009 12:02:32 PM | A | PASS |
|
|
Fire life safety okay for final, structural inspector to verify sign at the main entry door.
|