ELE13-02559
| Permanent Service | 11/25/2013 | 11/25/2013 | 11/25/2013 2:57:34 PM | P | PASS |
|
|
p/s u/g n ok
|
ELE13-03291
| Temporary Service | 11/24/2013 | 11/25/2013 | 11/25/2013 2:21:32 PM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov NEC 230.24(B)(1) Lowest point of the drip loop for overhead service 10 ft. Idaho Power requires minimum 6x6 pressure treated for temp. overhead service.
|
ELE13-03290
| Electrical Rough-In | 11/25/2013 | 11/25/2013 | 11/25/2013 2:13:24 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Don Conley rough-in ok cover
|
ELE13-03233
| Final | 11/25/2013 | 11/25/2013 | 11/25/2013 1:18:42 PM | P | FAIL |
|
|
Please final. Call Dave if you have any questions Phone #: ###-#### >> Inspection requested via web by David Mackey NEC 680.26 Equipotential bonding (water faucet)
|
ELE13-03233
| Electrical Rough-In | 11/25/2013 | 11/25/2013 | 11/25/2013 1:12:27 PM | P | PASS |
|
|
Please final. Call Dave if you have any questions Phone #: ###-#### >> Inspection requested via web by David Mackey rough-in ok cover last portion of trench
|
GCE13-00199
| GCE-Temporary Service | 11/25/2013 | 11/25/2013 | 11/25/2013 12:44:42 PM | P | PASS |
|
|
Terry ###-#### t/s u/g n ok
|
ELE13-03292
| Temporary Service | 11/25/2013 | 11/25/2013 | 11/25/2013 12:06:37 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by shane miller t/s o/h n ok
|
ELE13-03290
| Permanent Service | 11/24/2013 | 11/25/2013 | 11/25/2013 10:06:10 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Don Conley p/s u/g n ok
|
ELE13-03290
| Electrical Rough-In | 11/24/2013 | 11/25/2013 | 11/25/2013 10:00:50 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Don Conley NEC 334.30 NM cable shall be secured within 12in.of receptacle or light box. NEC 320.23 guard strips within 6 ft of attic access. Luminair boxes shall be supported from framing structure
|
ELE13-03289
| Electrical Rough-In | 11/24/2013 | 11/25/2013 | 11/25/2013 9:11:26 AM | A | PASS |
|
|
CALL FOR ACCESS ###-#### Phone #: ###-#### >> Inspection requested via web by John VanZandt rough-in ok cover recessed cans on back patio
|
ELE13-03276
| Permanent Service | 11/22/2013 | 11/25/2013 | 11/25/2013 8:51:09 AM | A | PASS |
|
|
Lock box on front door. Code 4062. Phone #: ###-#### >> Inspection requested via web by Heath Thomas p/s o/h rec ok
|
ELE13-02395
| Final | 11/23/2013 | 11/25/2013 | 11/25/2013 8:21:46 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Danny Perrine final ok duplex
|
ELE12-00964
| ELE-Aging Inspection | 11/25/2013 | 11/25/2013 | 11/25/2013 6:55:13 AM | | DONE |
|
|
still under construction
|