Inspections for the day of: Monday, November 25, 2013.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-02559 Permanent Service11/25/201311/25/201311/25/2013 2:57:34 PMPPASS
p/s u/g n ok
ELE13-03291 Temporary Service11/24/201311/25/201311/25/2013 2:21:32 PMAFAIL
Phone #: ###-#### >> Inspection requested via web by daniel bibikov NEC 230.24(B)(1) Lowest point of the drip loop for overhead service 10 ft. Idaho Power requires minimum 6x6 pressure treated for temp. overhead service.
ELE13-03290 Electrical Rough-In11/25/201311/25/201311/25/2013 2:13:24 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Don Conley rough-in ok cover
ELE13-03233 Final11/25/201311/25/201311/25/2013 1:18:42 PMPFAIL
Please final. Call Dave if you have any questions Phone #: ###-#### >> Inspection requested via web by David Mackey NEC 680.26 Equipotential bonding (water faucet)
ELE13-03233 Electrical Rough-In11/25/201311/25/201311/25/2013 1:12:27 PMPPASS
Please final. Call Dave if you have any questions Phone #: ###-#### >> Inspection requested via web by David Mackey rough-in ok cover last portion of trench
GCE13-00199 GCE-Temporary Service11/25/201311/25/201311/25/2013 12:44:42 PMPPASS
Terry ###-#### t/s u/g n ok
ELE13-03292 Temporary Service11/25/201311/25/201311/25/2013 12:06:37 PMPPASS
Phone #: ###-#### >> Inspection requested via web by shane miller t/s o/h n ok
ELE13-03290 Permanent Service11/24/201311/25/201311/25/2013 10:06:10 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Don Conley p/s u/g n ok
ELE13-03290 Electrical Rough-In11/24/201311/25/201311/25/2013 10:00:50 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Don Conley NEC 334.30 NM cable shall be secured within 12in.of receptacle or light box. NEC 320.23 guard strips within 6 ft of attic access. Luminair boxes shall be supported from framing structure
ELE13-03289 Electrical Rough-In11/24/201311/25/201311/25/2013 9:11:26 AMAPASS
CALL FOR ACCESS ###-#### Phone #: ###-#### >> Inspection requested via web by John VanZandt rough-in ok cover recessed cans on back patio
ELE13-03276 Permanent Service11/22/201311/25/201311/25/2013 8:51:09 AMAPASS
Lock box on front door. Code 4062. Phone #: ###-#### >> Inspection requested via web by Heath Thomas p/s o/h rec ok
ELE13-02395 Final11/23/201311/25/201311/25/2013 8:21:46 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Danny Perrine final ok duplex
ELE12-00964 ELE-Aging Inspection11/25/201311/25/201311/25/2013 6:55:13 AM DONE
still under construction