ELE14-03206
| Temporary Service | 11/25/2014 | 11/25/2014 | 11/25/2014 3:20:00 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tyler Bowen t/s o/h rec ok
|
ELE14-02213
| Electrical Rough-In | 11/25/2014 | 11/25/2014 | 11/25/2014 2:59:39 PM | P | FAIL |
|
|
mike Phone #: ###-#### 330.10- MC cable shall not be installed where subject to physical damage. Ballasts for recessed cans shall be installed in a manner that allows access for servicing.
|
ELE14-02896
| Final | 11/25/2014 | 11/25/2014 | 11/25/2014 2:13:05 PM | P | FAIL |
|
|
Building should be open call if you need access Phone #: ###-#### Inspection requested via web by robert feller 511.12- All 15 and 20 amp receptical outlets located in garage area shall have GFCI protection. BCC energy code- Duel switching or accupancy sencors shall control lighting
|
ELE14-03271
| Final | 11/25/2014 | 11/25/2014 | 11/25/2014 1:28:39 PM | P | FAIL |
|
|
Breanne-please call for access Phone #: ###-#### 110.3- Terminations at old hot tub disconnect not compliant. -30amp breaker on 14 ga. wire.. -NM cable ran in damp or wet location in flex. -Grounded conductor strands split ti seperate terminations. -Multiple conductors terminated under single lugs listed for single conductors.
|
ELE14-03271
| Permanent Service | 11/25/2014 | 11/25/2014 | 11/25/2014 1:20:53 PM | P | FAIL |
|
|
Breanne-please call for access Phone #: ###-#### 250.52- Unable to verify grounding electrode system. 2 ground rods required for reconnect.
|
ELE14-02963
| Electrical Rough-In | 11/24/2014 | 11/25/2014 | 11/25/2014 12:51:36 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Louis Keller BBC 4-05-31(D) has been removed from electrical ordinance per Daryl DeGrange. Addition Rough in ok cover
|
ELE14-02083
| Final | 11/24/2014 | 11/25/2014 | 11/25/2014 12:06:14 PM | A | PASS |
|
|
Owner will be home after 10:30. Inspection requested via web by Terry Scott Final ok
|
ELE14-02747
| Electrical Rough-In | 11/24/2014 | 11/25/2014 | 11/25/2014 10:27:01 AM | A | PASS |
|
|
expantion parking lot. underground// mike Phone #: ###-#### All underground on north section rough in ok cover
|
ELE14-02785
| Final | 11/25/2014 | 11/25/2014 | 11/25/2014 10:00:39 AM | A | PASS |
|
|
Please contact James ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Tracy Robertson no card posted. Final ok
|
ELE14-02786
| Final | 11/25/2014 | 11/25/2014 | 11/25/2014 10:00:03 AM | A | PASS |
|
|
Please contact James ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Tracy Robertson No card posted. Final ok
|
ELE14-03254
| Final | 11/24/2014 | 11/25/2014 | 11/25/2014 9:02:46 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON 210.8- All 15 and 20 amp receptical outlets installed in garage shall have GFCI protection. 110.3- NM cable stubbed out below meter shall be terminated in a box to protect wire from weather. Number provided not ele contractor.
|
ELE14-03103
| Electrical Rough-In | 11/24/2014 | 11/25/2014 | 11/25/2014 8:37:53 AM | A | PASS |
|
|
call first, ###-#### Phone #: ###-#### Inspection requested via web by PAT MILLER Up master bath floor heat rough in ok cover
|
ELE12-02382
| ELE-Aging Inspection | 11/25/2014 | 11/25/2014 | 11/25/2014 8:23:37 AM | | DONE |
|
|
Still under review
|
ELE13-00163
| ELE-Aging Inspection | 11/25/2014 | 11/25/2014 | 11/25/2014 8:22:53 AM | | DONE |
|
|
Still under construction
|
ELE14-03067
| Final | 11/25/2014 | 11/25/2014 | 11/25/2014 8:18:02 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt Final ok
|