Inspections for the day of: Monday, November 25, 2019.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-02723 Final11/22/201911/25/201911/25/2019 3:23:31 PMPPASS
Any questions feel free to call Bill at the above number. Phone #: ###-#### Inspection requested via web by Sherry Allen
Unit at South East corner of intercection near 12185 Hickory. No load present at time of inspection. Final ok
ELE19-00602 Electrical Rough-In11/22/201911/25/201911/25/2019 2:47:23 PMPPASS
6th floor east PT deck cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Pour noted rough in ok cover
ELE19-03585 Electrical Rough-In11/25/201911/25/201911/25/2019 2:05:20 PMPPASS
Ceiling grid Phone #: ###-#### Inspection requested via web by Jim Williams
Grid rough in ok cover
ELE19-03678 Electrical Rough-In11/22/201911/25/201911/25/2019 1:31:46 PMAFAIL
Would like to meet with Rock again. He gave me my preliminary meeting. I have the wires pulled through the walls and getting close to outlets and closing in. Thanks. Phone #: ###-#### Inspection requested via web by Curtis Hoovestol Building permit finaled in january.
250.24(A)(5)- Grounding and grounded conductors shall be connected on load side of service. Need a equipment grounding conductor to sub panel in shop.
250.118- All non current carrying metal parts of equiment shall be connected to as equipment grounding conductor. Complete make-up so inspector can inspect connections.
314.29- Covers for conduit bodies shall remain accessible, Owner to build access for LB under panel.
334.30- NM cables shall be secured with in 12'" of entering panel.
406.12- All receptacle outlets installed in a residential garage shall be tamper resistant type.
ELE19-04204 Electrical Rough-In11/22/201911/25/201911/25/2019 9:56:34 AMAFAIL
Phone #: ###-#### Inspection requested via web by Barbara Szurgot
Box front garage light.
Secure NM above small panel.
NM sheathing shall enter boxes a min of 1/4"
Torque main bonding jumper screws.
Secure dryer box.
Recessed can covers shall be completely installed, up loft, above master vanity, kitchen.
Furnace temp hook up shall be in a box.
no more than 12' between receptacle outlets in S.E. rm.
ELE19-04394 Rough-In Permanent Service11/22/201911/25/201911/25/2019 8:49:01 AMAPASS
Phone #: ###-#### Inspection requested via web by danny perrine
Rough in ok cover p/s u/g n ok