BLD19-02562
| FIRE-Final Inspection | 11/25/2019 | 11/25/2019 | 11/25/2019 3:36:44 PM | P | PASS |
|
|
Previously noted items have been corrected, final life fire safety inspection for area of work complete.
Rob Phone #: ###-####
|
BLD19-04620
| FIRE-Final Inspection | 11/25/2019 | 11/25/2019 | 11/25/2019 12:51:55 PM | P | PASS |
|
|
No fire sprinkler modificaitons, no fire alarm modifications, fire extinguisher is placed with a current inspection tag, signage to be placed at main entry reading "Door to remain unlocked while building is occupied" as discussed. Final life fire safety inspection for area of work complete, signatures provided for associated trades on permit sign off card.
Matt Phone #: ###-####
|
FIR19-00766
| INSP-Sprinkler Rough-in | 11/25/2019 | 11/25/2019 | 11/25/2019 12:28:56 PM | P | FAIL |
|
|
Areas of concern for tenting were shown to the point of contact during last inspection, tenting still is not correct, no cover is approved.
Contact Perly Daniel ###-#### 30 min prior to RTC Insp start please,
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR19-00721
| INSP-Final Inspection | 11/25/2019 | 11/25/2019 | 11/25/2019 9:26:03 AM | P | CANC |
|
|
Cancelled per conversation with point of contact, inspection will be rescheduled for a later date.
Rick Phone #: ###-####
|
FIR19-00394
| INSP-Final Inspection | 11/22/2019 | 11/25/2019 | 11/25/2019 8:57:52 AM | A | CANC |
|
|
Permit has been finaled in 22NOV2019.
UG inspections are complete. Flush completed on overhead permit. Please call Jeff with questions.
Thanks Phone #: ###-#### Inspection requested via web by Jeff Packham
|
FIR19-00867
| INSP-Sprinkler Rough-in | 11/25/2019 | 11/25/2019 | 11/25/2019 8:57:17 AM | A | FAIL |
|
|
Underground not installed at timne of inspection.
Call before heading out, underground rough to bury (hydro in warm weather or closer to final) Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00869
| INSP-Sprinkler Rough-in | 11/25/2019 | 11/25/2019 | 11/25/2019 8:56:45 AM | A | FAIL |
|
|
Bury depth of 54 inches to top of pipe not met. Attach bury wire to pipe, cover is not approved.
Call before heading out, underground rough to bury (hydro in warm weather or closer to final) Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00870
| INSP-Sprinkler Rough-in | 11/25/2019 | 11/25/2019 | 11/25/2019 8:56:25 AM | A | FAIL |
|
|
Bury depth of 54 inches to top of pipe not met. Attach bury wire to pipe, cover is not approved.
Call before heading out, underground rough to bury (hydro in warm weather or closer to final) Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00864
| INSP-Sprinkler Rough-in | 11/25/2019 | 11/25/2019 | 11/25/2019 8:56:05 AM | A | FAIL |
|
|
Underground not installed at time of inspection.
Call before heading out, underground rough to bury (hydro in warm weather or closer to final) Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00871
| INSP-Sprinkler Rough-in | 11/25/2019 | 11/25/2019 | 11/25/2019 8:54:51 AM | A | FAIL |
|
|
Bury depth of 54 inches to top of pipe not met. Attach bury wire to pipe, cover is not approved.
Call before heading out, underground rough to bury (hydro in warm weather or closer to final) Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00872
| INSP-Sprinkler Rough-in | 11/25/2019 | 11/25/2019 | 11/25/2019 8:54:28 AM | A | FAIL |
|
|
Bury depth of 54 inches to top of pipe not met. Attach bury wire to pipe, cover is not approved.
Call before heading out, underground rough to bury (hydro in warm weather or closer to final) Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|