Inspections for the day of: Tuesday, November 26, 2002.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-03607 Final11/19/200211/26/200211/26/2002 12:00:00 AMAPASS
###-#### ok 11/26/2002 11:12:37 AM
ELE02-03139 Electrical Rough-In11/25/200211/26/200211/26/2002 12:00:00 AMAPART
###-#### follow up r/i 314.43 no screws allowed in non metallic boxes and watch box fill 11/26/2002 11:49:22 AM
ELE02-03633 Rough-In Permanent Service11/25/200211/26/200211/26/2002 12:00:00 AMAPASS
###-#### electrode ok for cover

p/s u/g new ok 11/26/2002 12:46:43 PM
ELE02-03109 Temporary Service11/25/200211/26/200211/26/2002 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 11/25/2002 at 14:48:50. Contact: ###-####. cor. posted called 310.12(C) & 250.119 shall not use green for phase conductors, 110.12(A) seal ko 11/26/2002 12:14:59 PM
ELE02-02775 Final11/26/200211/26/200211/26/2002 12:00:00 AMPFAIL
fn charles- ###-#### 210.11(C)(3) requires 20 amp circuit for new bathroom, 110.3(B) fan light over shower requires gfci , per manufactures instructions met with owner correction posted 11/26/2002 4:33:27 PM
ELE02-02246 Final11/26/200211/26/200211/26/2002 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok 11/26/2002 3:46:29 PM
ELE02-02685 Electrical Rough-In11/26/200211/26/200211/26/2002 12:00:00 AMPPART
conference ok correction posted 110.26(E),(F)(1) for electrical gear added oon 2 nd floor
ELE02-03154 Electrical Rough-In11/25/200211/26/200211/26/2002 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 11/25/2002 at 13:01:14. Contact: ###-####. conference ok for new building used as sewing next to house 11/26/2002 3:26:05 PM
ELE02-01560 Final11/25/200211/26/200211/26/2002 12:00:00 AMPPASS
PETE ###-#### ok 11/26/2002 6:02:43 PM