FIR03-00465
| INSP-Alarm Testing | 11/26/2003 | 11/26/2003 | 11/28/2003 12:00:00 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Daniel Buccino H/S coverage was adequate as the strobe behind stocker was increased to 30 cd 11/28/2003 9:52:53 AM
|
FIR03-00457
| INSP-Alarm Testing | 11/26/2003 | 11/26/2003 | 11/28/2003 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 11/26/2003 at 8:32:06 AM. Contact: ###-####. addresses 51 and 52 were used 11/28/2003 9:53:18 AM
|
FIR03-00497
| FIR-Aging Inspection | 11/26/2003 | 11/26/2003 | 11/26/2003 12:00:00 AM | | PASS |
|
|
talked to Greg of TVFP and he said this permit should be cancelled; told him to contact the permit desk to void this permit 12/2/2003 7:16:39 AM
|
FIR03-00662
| INSP-Sprinkler Rough-in/Hydro | 11/25/2003 | 11/26/2003 | 11/26/2003 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/25/2003 at 2:54:01 PM. Contact: ###-####.
|
FIR03-00305
| INSP-Sprinkler Rough-in | 11/25/2003 | 11/26/2003 | 11/26/2003 12:00:00 AM | A | PART |
|
|
phase one is okay to cover; see plans for area 11/26/2003 9:21:41 AM
|
BLD03-01063
| FIRE-Final Inspection | 11/25/2003 | 11/26/2003 | 11/26/2003 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/25/2003 at 9:53:02 PM. Contact: ###-####.
|
FIR03-00487
| INSP-Final Inspection | 11/26/2003 | 11/26/2003 | 11/26/2003 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 11/26/2003 at 8:59:41 AM. Contact: ###-####. need to relocate smoke detector away from diffuser at FACP; need map of initiating devices; record of completion when complete 11/26/2003 4:31:24 PM
|
BLD03-00498
| FIRE-Final Inspection | 11/26/2003 | 11/26/2003 | 11/26/2003 12:00:00 AM | P | NR |
|
|
Scheduled by a contractor via Hello! on 11/26/2003 at 9:28:20 AM. Contact: ###-####. need alarm plans per plans review notes 11/26/2003 2:14:54 PM
|
BLD03-02298
| FIRE-Final Inspection | 11/26/2003 | 11/26/2003 | 11/26/2003 12:00:00 AM | P | PART |
|
|
per Dave Miller fire/life safety will be on temp occupancy pending submittal/approval of fire alarm plans
|
BLD03-01716
| FIRE-Final Inspection | 11/26/2003 | 11/26/2003 | 11/26/2003 12:00:00 AM | P | FAIL |
|
|
complete alarm issues under fire alarm permit; clarify exit sign on corridor side of multi-purpose room (exit through room with doors swinging out?); right leaf of doors with panic hardware won't open with left leaf closed; smoke seals on corridor doors if one hour corridor; draft stops not complete; occupant load sign in multi-purpose room; panic required on corridor door out of multi-purpose room and has slide dead bolt; need emergency light in west corridor;
|