Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00270 INSP-Final Inspection11/25/200311/26/200311/26/2003 9:41:26 AMACANC
This is Grants Cell, After 10:00 a.m. if possiable.; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
BLD02-01063 FIRE-Final Inspection11/26/200311/26/200311/26/2003 12:00:00 AM  
Final - approved by Troy Cobbley
FIR03-00705 INSP-Sprinkler Rough-in/Hydro11/25/200311/26/200311/26/2003 12:00:00 AMACANC
duplicate inspection 11/26/2003 11:38:29 AM
FIR03-00645 INSP-Sprinkler Rough-in/Hydro11/25/200311/26/200311/26/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 11/25/2003 at 8:57:16 AM. Contact: ###-####.
FIR01-00124 INSP-Sprinkler Rough-in11/25/200311/26/200311/26/2003 12:00:00 AMAFAIL
dave ###-#### Final inspection needs to be done which is to include signs on riser, head box with heads and wrench, knox box, inspection tag for riser, site glass, test bell, lock control valves in open position and anything else the review notes may have. The original installing contractor that started the project is now out of business 11/26/2003 3:17:21 PM
FIR03-00705 INSP-Final Inspection11/26/200311/26/200311/26/2003 12:00:00 AMAPASS
BLD03-02256 FIRE-Final Inspection11/25/200311/26/200311/26/2003 12:00:00 AMAPASS
Fire life safety and fire sprinkler finaled 11/26/2003 9:03:22 AM
FIR03-00669 INSP-Supply line flush11/25/200311/26/200311/26/2003 12:00:00 AMAPASS
supply line flush is OK 11/26/2003 9:57:34 AM
BLD03-00986 FIRE-Final Inspection11/25/200311/26/200311/26/2003 12:00:00 AMAPASS
fire life safety finaled 11/26/2003 12:21:59 PM
BLD03-00986 FIRE-Final Inspection11/25/200311/26/200311/26/2003 12:00:00 AMAPASS
fire life safety finaled 11/26/2003 12:21:59 PM
FIR03-00636 INSP-Final Inspection11/26/200311/26/200311/26/2003 12:00:00 AMAPASS
BLD03-01564 FIRE-Final Inspection11/26/200311/26/200311/26/2003 12:00:00 AMAPASS
fire life safety finaled
BLD03-02674 FIRE-Final Inspection11/26/200311/26/200311/26/2003 12:00:00 AMAFAIL
remove the wood from above the ceiling or fire proof, patch hole to attic that is above the ceiling in the southwest corner, remove the door magnets or provide city approved plans with fire alarm intergration, mount fire extinguisher
BLD03-02348 FIRE-Final Inspection11/26/200311/26/200311/26/2003 12:00:00 AMAFAIL
provide approved plans for life safety review, provide canopies for the pendant sprinkler heads and remove the door magnets or provide city approved plans showing the fire alarm intergration
FIR03-00268 INSP-Final Inspection11/26/200311/26/200311/26/2003 12:00:00 AMPPASS
FIR03-00277 INSP-Final Inspection11/26/200311/26/200311/26/2003 12:00:00 AMPPASS
BLD02-02720 FIRE-Final Inspection11/26/200311/26/200311/26/2003 12:00:00 AMPPASS
fire life safety and fire alarm finaled
BLD02-01070 FIRE-Final Inspection11/26/200311/26/200311/26/2003 12:00:00 AMPPASS
fire life safety and fire alarm finaled
BLD02-02719 FIRE-Final Inspection11/26/200311/26/200311/26/2003 12:00:00 AMPPASS
fire alarm and fire life safety is ok
BLD02-02715 FIRE-Final Inspection11/26/200311/26/200311/26/2003 12:00:00 AMPPASS
fire life safety and fire alarm finaled
BLD03-02623 FIRE-Final Inspection11/26/200311/26/200311/26/2003 12:00:00 AMPFAIL
provide air balance reports, provide barriers on both sides of the fryer, provide occupant load sign, tag the existing fire extinguisher, mount the K type fire extinguisher, Per dave miller a temp occupancy is ok until the fire alarm system interconnection is approved
FIR03-00270 INSP-Final Inspection11/26/200311/26/200311/26/2003 12:00:00 AMPPASS
grant; Phone #: ###-#### Internet Inspection Request from: Darla Downs
FIR03-00687 INSP-Final Inspection11/26/200311/26/200311/26/2003 12:00:00 AMPFAIL
don; Phone #: ###-#### Per dave miller a temp occupancy is ok until the fire alarm system interconnection is approved. Need air balance reports and the hood connected to the fire alarm but see note above. 11/26/2003 4:32:59 PM