ELE04-01886
| ELE-Aging Inspection | 11/26/2004 | 11/26/2004 | 11/26/2004 12:00:00 AM | | CANC |
|
|
called no response 11/26/2004 1:53:55 PM
|
ELE04-02491
| Final | 11/23/2004 | 11/26/2004 | 11/26/2004 12:00:00 AM | A | PASS |
|
|
Internet Inspection Request from: KENT JONES ok 11/26/2004 9:39:31 AM
|
ELE04-03693
| Temporary Service | 11/24/2004 | 11/26/2004 | 11/26/2004 12:00:00 AM | A | FAIL |
|
|
jackie- ###-#### needs grd rod and G E C, remove cord not being used, or terminate in a box 11/26/2004 9:07:45 AM
|
ELE04-03512
| Electrical Rough-In | 11/24/2004 | 11/26/2004 | 11/26/2004 12:00:00 AM | A | PART |
|
|
underground --jackie ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok 11/26/2004 9:07:55 AM
|
ELE04-03665
| Electrical Rough-In | 11/24/2004 | 11/26/2004 | 11/26/2004 12:00:00 AM | A | NR |
|
|
Jack call before you go out; Phone #: ###-#### Internet Inspection Request from: Jan Rice called wants PM inspection 11/26/2004 8:38:53 AM
|
ELE04-03678
| Electrical Rough-In | 11/24/2004 | 11/26/2004 | 11/26/2004 12:00:00 AM | A | DONE |
|
|
CONTACT: SHANE KORTE; Phone #: ###-#### Internet Inspection Request from: Deb McCoy was 11-24-04
11/26/2004 7:40:08 AM
|
ELE04-03512
| Final | 11/26/2004 | 11/26/2004 | 11/26/2004 12:00:00 AM | P | CANC |
|
|
Brett/temp power; Phone #: ###-#### Internet Inspection Request from: Jan Rice wrong permit number this is job number see added inspection to PM ele04-03693 11/26/2004 12:51:58 PM
|
ELE04-03693
| Temporary Service | 11/26/2004 | 11/26/2004 | 11/26/2004 12:00:00 AM | P | FAIL |
|
|
cor. posted called shall use t/s permit not job permit, 110.12(A) seal all unused KOs, use in use covers, instake bond bushings both ends of emt that GEC is in 250.92(A)(3)
|