FIR05-00033
| INSP-Conference | 11/26/2007 | 11/26/2007 | 11/26/2007 4:09:21 PM | P | DONE |
|
|
Job scheduling.
|
FIR07-00333
| INSP-Alarm Testing | 11/26/2007 | 11/26/2007 | 11/26/2007 3:54:18 PM | P | DEFR |
|
|
Inspection request intended for the shell and core alarm work, items tested today include fire sprinkler monitoring of the fire pump, controller, power supplies, dry system, tampers, flows, etc. Outside bell does not function at pump flow switch, need 12 ah batteries at the FACP, tamper at the standpipe control valve is not correct.
|
FIR06-00504
| INSP-Final Inspection | 11/21/2007 | 11/26/2007 | 11/26/2007 3:46:04 PM | A | PART |
|
|
Completed sprinkler monitoring testing including the dry system, fire pump, controller and power supplies, noted a QOD is not required on the dry system, missing coverage at the stairs to the basement electrical room, need signage at valves, missing head boxes, finish pack, need to complete forward flow of the BFP, also need to complete a final shell system walkthrough.
|
FIR07-00939
| INSP-Final Inspection | 11/26/2007 | 11/26/2007 | 11/26/2007 3:39:52 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD07-02607
| FIRE-Final Inspection | 11/26/2007 | 11/26/2007 | 11/26/2007 1:17:27 PM | P | FAIL |
|
|
Provide signage at the main entry/exit door, repair one exit sign and one EM light at the office area entrance, provide one 2A10BC PFE for the 1st floor offices, remove existing fire extinguisher signage at four locations in the warehouse area where no longer applicable, missing one exit discharge light at the west side.
|
FIR07-00469
| FIR-Aging Inspection | 11/26/2007 | 11/26/2007 | 11/26/2007 11:57:40 AM | | DEFR |
|
|
Work in progress
|