Inspections for the day of: Monday, November 26, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00459 INSP-Conference11/26/200711/26/200711/27/2007 11:03:55 AMPDONE
I witnessed the fire retardent being applied. The product being used is called "Flame Stop II" produced by Flame Stop Inc. Per the data sheet the product appears to meet NFPA 13 requirements. These exterior concealed spaces are ok to cover.
BLD07-00735 FIRE-Final Inspection11/26/200711/26/200711/26/2007 4:11:41 PMPFAIL
The exit discharge lighting needs to be repaired.
BLD07-02439 FIRE-Conference11/21/200711/26/200711/26/2007 4:08:44 PMPDONE
I went over the life safety requirements with tom.
FIR07-00449 INSP-Sprinkler Rough-in11/21/200711/26/200711/26/2007 3:24:16 PMPPASS
Todays inspection was for the hanger attachments that will be buried above the insulation in the north side girls and boys restrooms. The hanger attachments are ok to cover.
BLD07-02358 FIRE-Final Inspection11/26/200711/26/200711/26/2007 3:22:47 PMPFAIL
Provide approved hardware on both the single and the double doors that exit out of the tenant space to the west. Provide an egress agreement as discussed for the common restroom area. Provide city approved plans for the wall changes.
FIR07-00904 INSP-Alarm Testing11/26/200711/26/200711/26/2007 3:18:30 PMPFAIL
Troy, knox box has been ordered I will call when installed also, phone trbl and 9x11 prints are taken care of. Thanks Robert Phone #: ###-#### Internet Inspection Request from: Robert Gobler
BLD07-00772 FIRE-Final Inspection11/23/200711/26/200711/26/2007 2:03:05 PMAPART
See the city approved for the lobby location, circled with yellow hilighter, that is ok to occupy. It has also been signed with todays date.
FIR07-00739 INSP-Final Inspection11/26/200711/26/200711/26/2007 1:26:44 PMPPASS
Permit passed. Forward flush passed.
FIR07-00904 INSP-Final Inspection11/26/200711/26/200711/26/2007 12:41:32 PMPFAIL
Provide knox box, map at the facp, as-built plans reflecting the actual zones used and repair phone line #1
FIR07-00517 INSP-Supply line flush11/21/200711/26/200711/26/2007 12:25:53 PMAPASS
The hydro tests of the underground and both overhead systems passed. The underground flush passed as well.
BLD07-02297 FIRE-Final Inspection11/21/200711/26/200711/26/2007 10:12:28 AMAPASS
life safety passed
FIR07-00919 INSP-Final Inspection11/21/200711/26/200711/26/2007 10:10:32 AMAPASS
permit finaled. Horns are not in sync but it is not required since this system was installed prior to this requirement as discussed wiht sam rogers.