FIR07-00459
| INSP-Conference | 11/26/2007 | 11/26/2007 | 11/27/2007 11:03:55 AM | P | DONE |
|
|
I witnessed the fire retardent being applied. The product being used is called "Flame Stop II" produced by Flame Stop Inc. Per the data sheet the product appears to meet NFPA 13 requirements. These exterior concealed spaces are ok to cover.
|
BLD07-00735
| FIRE-Final Inspection | 11/26/2007 | 11/26/2007 | 11/26/2007 4:11:41 PM | P | FAIL |
|
|
The exit discharge lighting needs to be repaired.
|
BLD07-02439
| FIRE-Conference | 11/21/2007 | 11/26/2007 | 11/26/2007 4:08:44 PM | P | DONE |
|
|
I went over the life safety requirements with tom.
|
FIR07-00449
| INSP-Sprinkler Rough-in | 11/21/2007 | 11/26/2007 | 11/26/2007 3:24:16 PM | P | PASS |
|
|
Todays inspection was for the hanger attachments that will be buried above the insulation in the north side girls and boys restrooms. The hanger attachments are ok to cover.
|
BLD07-02358
| FIRE-Final Inspection | 11/26/2007 | 11/26/2007 | 11/26/2007 3:22:47 PM | P | FAIL |
|
|
Provide approved hardware on both the single and the double doors that exit out of the tenant space to the west. Provide an egress agreement as discussed for the common restroom area. Provide city approved plans for the wall changes.
|
FIR07-00904
| INSP-Alarm Testing | 11/26/2007 | 11/26/2007 | 11/26/2007 3:18:30 PM | P | FAIL |
|
|
Troy, knox box has been ordered I will call when installed also, phone trbl and 9x11 prints are taken care of. Thanks Robert Phone #: ###-#### Internet Inspection Request from: Robert Gobler
|
BLD07-00772
| FIRE-Final Inspection | 11/23/2007 | 11/26/2007 | 11/26/2007 2:03:05 PM | A | PART |
|
|
See the city approved for the lobby location, circled with yellow hilighter, that is ok to occupy. It has also been signed with todays date.
|
FIR07-00739
| INSP-Final Inspection | 11/26/2007 | 11/26/2007 | 11/26/2007 1:26:44 PM | P | PASS |
|
|
Permit passed. Forward flush passed.
|
FIR07-00904
| INSP-Final Inspection | 11/26/2007 | 11/26/2007 | 11/26/2007 12:41:32 PM | P | FAIL |
|
|
Provide knox box, map at the facp, as-built plans reflecting the actual zones used and repair phone line #1
|
FIR07-00517
| INSP-Supply line flush | 11/21/2007 | 11/26/2007 | 11/26/2007 12:25:53 PM | A | PASS |
|
|
The hydro tests of the underground and both overhead systems passed. The underground flush passed as well.
|
BLD07-02297
| FIRE-Final Inspection | 11/21/2007 | 11/26/2007 | 11/26/2007 10:12:28 AM | A | PASS |
|
|
life safety passed
|
FIR07-00919
| INSP-Final Inspection | 11/21/2007 | 11/26/2007 | 11/26/2007 10:10:32 AM | A | PASS |
|
|
permit finaled. Horns are not in sync but it is not required since this system was installed prior to this requirement as discussed wiht sam rogers.
|