Inspections for the day of: Wednesday, November 26, 2008.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00550 FIR-Aging Inspection11/26/200811/26/200812/1/2008 11:33:37 AM NR
I contacted peak alarm and they said that they would be on the job at the end of December or January as per their contact. I said "so this building has a non-functioning fire alarm system?" And they said yes.

I have forwarded this information to sam rogers and mark sentenno for further action.

BLD08-00560 FIRE-Final Inspection11/26/200811/26/200811/26/2008 5:24:33 PMPPART
Per sam rogers a temporary is given until the exit discharge lighting as per the approved plans has been installed and tested.
FIR07-00766 INSP-Sprinkler Rough-in/Hydro11/26/200811/26/200811/26/2008 4:08:23 PMPFAIL
Flow switch has not been wired to the alarm bell, not all ceilings have been finished, missing escheons and exposed cpvc piping under the east basement stairs. Also a sprinkler head at the top of the west stairs, first floor, needs to be relocated away from a can light or an intermediate temperature head needs to be installed as per 7.5.5.3 of NFPA 13D.
BLD08-00698 FIRE-Final Inspection11/25/200811/26/200811/26/2008 4:05:58 PMAFAIL
See the correction notice for the items needing addressed which include providing the city approved drawings for a complete inspection, repair the exit signs, provide emergency lighting in the common areas as discussed, provide missing exit sign/emergency light from the dining area, mount fire extinguishers, complete the one hour fire sprinkler riser room, provide hardware on the exterior gate on the west side of building, provide 911 sticker for the fire sprinkler alarm bell
FIR08-00657 INSP-Final Inspection11/26/200811/26/200811/26/2008 4:01:55 PMPPASS
Permit finaled
BLD08-00890 FIRE-Final Inspection11/25/200811/26/200811/26/2008 4:01:23 PMPFAIL
See the city approved drawings, sheet A0.0 for the written correction notice which includes deadbolts need to be removed, exit discharge lighting required, building address required, provide sticker at the main exit and provide complete paving and curbing of the fire dept turn around.
BLD08-00575 FIRE-Final Inspection11/26/200811/26/200811/26/2008 2:02:22 PMPFAIL
See the correction notice listed on the first page of the city approved plans.
FIR08-00563 INSP-Final Inspection11/25/200811/26/200811/26/2008 12:47:02 PMAPASS
Permit finaled
FIR08-00772 INSP-Conference11/25/200811/26/200811/26/2008 11:51:12 AMACANC
Cancel per Mike
FIR08-00629 INSP-Sprinkler Rough-in11/25/200811/26/200811/26/2008 11:48:03 AMAPASS
See the city approved plans for the 3rd floor lobby piping that can be covered.
BLD08-01809 FIRE-Final Inspection11/25/200811/26/200811/26/2008 10:30:26 AMAFAIL
See the city approved plans for the correction notice listed on the front sheet.
BLD08-00576 FIRE-Final Inspection11/25/200811/26/200811/26/2008 10:30:05 AMAFAIL
See the city approved plans for the correction notice listed on the front sheet.
FIR08-00717 INSP-Final Inspection11/25/200811/26/200811/26/2008 10:29:20 AMAPASS
Permit finaled. The strobes now sync and temporal is being used.
BLD08-01790 FIRE-Final Inspection11/24/200811/26/200811/25/2008 1:19:43 PMPFAIL
Provide apartment numbers, provide fire extinguishers as discussed and relocate the new smoke detectors in the corridor atleast 3' away from the bathroom doors. Also provide approved plans on site for inspection.