Inspections for the day of: Friday, November 26, 2010.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00568 INSP-Final Inspection11/26/201011/26/201011/26/2010 4:56:12 PMPPART
Final pending finishes.
BLD10-02103 FIRE-Conference11/26/201011/26/201011/26/2010 4:51:47 PMPPART
Project related fire alarm and sprinkler permits finaled.
BLD10-02423 FIRE-Final Inspection11/26/201011/26/201011/26/2010 4:49:44 PMPNR
Pending project related fire sprinkler permit.
FIR07-00273 FIR-Aging Inspection11/26/201011/26/201011/26/2010 11:48:33 AM PEND
Need site inspection request.
FIR10-00554 INSP-Final Inspection11/24/201011/26/201011/26/2010 11:44:03 AMANH
Phoned contact and no answer. Stopped by jobsite- no access, building is closed for the holiday. Rescheduled 11/29.
BLD10-02500 FIRE-Final Inspection11/24/201011/26/201011/26/2010 11:41:02 AMAFAIL
Correction items include; spin one exit sign 180 deg., provide directional chevrons per plan at exit sign in the middle corridor, noted modifications to the exisitng sprinkler coverage will be required due to the remodel work- one overspaced head and two heads which exceed min. separation distance, post PFE with current tag at the 2nd floor, provide approved hardware at the main entry/exit 2nd floor suite, exit sign at the 2nd floor is shown on plans- however is not installed or required, missing escutcheons at some locations. Existing building fire sprinkler system is overdue annual inspection/certification.
BLD10-02365 FIRE-Final Inspection11/24/201011/26/201011/26/2010 11:31:14 AMAFAIL
Fire sprinkler system will require modification due to remodel work, existing system is overdue required annual certification.