FIR10-00568
| INSP-Final Inspection | 11/26/2010 | 11/26/2010 | 11/26/2010 4:56:12 PM | P | PART |
|
|
Final pending finishes.
|
BLD10-02103
| FIRE-Conference | 11/26/2010 | 11/26/2010 | 11/26/2010 4:51:47 PM | P | PART |
|
|
Project related fire alarm and sprinkler permits finaled.
|
BLD10-02423
| FIRE-Final Inspection | 11/26/2010 | 11/26/2010 | 11/26/2010 4:49:44 PM | P | NR |
|
|
Pending project related fire sprinkler permit.
|
FIR07-00273
| FIR-Aging Inspection | 11/26/2010 | 11/26/2010 | 11/26/2010 11:48:33 AM | | PEND |
|
|
Need site inspection request.
|
FIR10-00554
| INSP-Final Inspection | 11/24/2010 | 11/26/2010 | 11/26/2010 11:44:03 AM | A | NH |
|
|
Phoned contact and no answer. Stopped by jobsite- no access, building is closed for the holiday. Rescheduled 11/29.
|
BLD10-02500
| FIRE-Final Inspection | 11/24/2010 | 11/26/2010 | 11/26/2010 11:41:02 AM | A | FAIL |
|
|
Correction items include; spin one exit sign 180 deg., provide directional chevrons per plan at exit sign in the middle corridor, noted modifications to the exisitng sprinkler coverage will be required due to the remodel work- one overspaced head and two heads which exceed min. separation distance, post PFE with current tag at the 2nd floor, provide approved hardware at the main entry/exit 2nd floor suite, exit sign at the 2nd floor is shown on plans- however is not installed or required, missing escutcheons at some locations. Existing building fire sprinkler system is overdue annual inspection/certification.
|
BLD10-02365
| FIRE-Final Inspection | 11/24/2010 | 11/26/2010 | 11/26/2010 11:31:14 AM | A | FAIL |
|
|
Fire sprinkler system will require modification due to remodel work, existing system is overdue required annual certification.
|