ELE96-02630
| INSP - Final | 11/26/1996 | 11/27/1996 | 11/27/1996 12:00:00 AM | A | FAIL |
|
|
11/26/96 315 - 14 failed jf cor. posted NEC, 210-8(a) (1), 210-7(d)(2), shall have power
|
ELE96-03248
| INSP - Final | 11/26/1996 | 11/27/1996 | 11/27/1996 12:00:00 AM | A | PASS |
|
|
11/26/96 315 - RE-INSPECTION 14 ok jf
|
ELE96-03913
| INSP - Ele Rough-In/Perm Svc | 11/26/1996 | 11/27/1996 | 11/27/1996 12:00:00 AM | A | PASS |
|
|
11/26/96 315 - RE-INSPECTION 09&53 ok jf 16rms 1a/c 200a u/g new
|
ELE96-03363
| INSP - Final | 11/27/1996 | 11/27/1996 | 11/27/1996 12:00:00 AM | P | FAIL |
|
|
11/27/96 315 - THERE IS A KEY UNDER THE PAINT CAN LID BY THE SIDE GARAGE FEE IS PAID.MPS 14 failed cor. posted NEC, 440-22(C), wire and provide maximum 25 amp for a/c 200-3 correct open neutral 2 outlets living room
|
ELE96-03378
| INSP - Final | 11/27/1996 | 11/27/1996 | 11/27/1996 12:00:00 AM | P | NH |
|
|
11/27/96 315 - nalc jf
|
ELE96-03345
| INSP - Final | 11/27/1996 | 11/27/1996 | 11/27/1996 12:00:00 AM | P | PASS |
|
|
11/27/96 315 - 14 ok jf
|
ELE96-02967
| INSP - Final | 11/27/1996 | 11/27/1996 | 11/27/1996 12:00:00 AM | P | PASS |
|
|
11/27/96 315 - REINSPECTION 14 ok jf
|
ELE96-03129
| INSP - Final | 11/27/1996 | 11/27/1996 | 11/27/1996 12:00:00 AM | P | FAIL |
|
|
11/27/96 315 - 14 failed jf cor. posted NEC,410-8 clearence light downst 370-29 no access to jbox behind cabinet under kitchen sink, BCC, no powe fan&light upstairs bath off of hallway, fix panel cover install cover on under kitchen sin
|
ELE96-03363
| INSP - Final | 11/26/1996 | 11/27/1996 | 11/26/1996 12:00:00 AM | P | CANC |
|
|
no reinspection until 30.00 reinspection fee paid. left message on contractors machine, also on their correct notice. per jafrank- ajb
|