BLD00-02820
| FIRE-Final Inspection | 11/26/2001 | 11/27/2001 | 11/27/2001 12:00:00 AM | A | PASS |
|
|
Life/safety finaled. OK for perm occ. 11/27/2001 9:44:27 AM
|
FIR01-00462
| INSP-Sprinkler Rough-in | 11/26/2001 | 11/27/2001 | 11/27/2001 12:00:00 AM | A | PASS |
|
|
Performed underground flush. Underground flush OK 11/27/2001 11:01:09 AM
|
BLD01-00084
| FIRE-Final Inspection | 11/26/2001 | 11/27/2001 | 11/27/2001 12:00:00 AM | A | FAIL |
|
|
Sprinkler head in front lobby overspaced, sprinkler head in rear of open office overspaced, fire extinguisher is mounted too high, provide NFPA 72 forms for the fire alarm system and perform annual inspection of fire sprinkler riser and tag 11/27/2001 10:25:15 AM
|
BLD01-01643
| FIRE-Final Inspection | 11/26/2001 | 11/27/2001 | 11/27/2001 12:00:00 AM | P | CANC |
|
|
To be rescheduled by contractor 11/27/2001 2:46:23 PM
|
FIR01-00556
| INSP-Final Inspection | 11/27/2001 | 11/27/2001 | 11/27/2001 12:00:00 AM | P | PASS |
|
|
Fire alarm system finaled. OK for perm occ 11/27/2001 4:47:41 PM
|
BLD01-01418
| FIRE-Final Inspection | 11/27/2001 | 11/27/2001 | 11/27/2001 12:00:00 AM | P | NR |
|
|
No approved fire alarm or fire sprinkler plans on site, no record of completion, main door does not have closer installed. Did not finish inspection 11/27/2001 3:48:23 PM
|
BLD01-02633
| FIRE-Sprinkler Rough-in | 11/27/2001 | 11/27/2001 | 11/27/2001 12:00:00 AM | P | PASS |
|
|
Rough-in OK. OK to cover 11/27/2001 12:11:03 PM
|
BLD01-02292
| FIRE-Alarm Testing | 11/27/2001 | 11/27/2001 | 11/27/2001 12:00:00 AM | P | PASS |
|
|
Added by Inspector: 430 On 11/27/2001 4:47:08 PM FIre alarm system finaled. OK for perm occ
|