Inspections for the day of: Monday, November 27, 2006.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-04369 Final11/27/200611/27/200611/27/2006 4:11:28 PMPPASS
bill - after 3:00 ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called contr, survey, over 360 degree bends in conduit, nec 358.26 told contr to address, ok to final
ELE06-04375 Electrical Rough-In11/27/200611/27/200611/27/2006 3:57:53 PMPCANC
Work performed by Kyle Sharp.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz done in am this date
ELE06-03582 Final11/27/200611/27/200611/27/2006 3:10:25 PMPPASS
ray ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
ELE06-03898 Electrical Rough-In11/22/200611/27/200611/27/2006 2:25:03 PMPPASS
Work performed by Kyle Sharp.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz see final
ELE06-03898 Final11/27/200611/27/200611/27/2006 2:24:24 PMPPASS
Work performed by Kyle Sharp.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz ok to final
ELE06-04121 Final11/27/200611/27/200611/27/2006 2:03:25 PMPPASS
any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok to final, no card to sign
ELE06-02468 Electrical Rough-In11/27/200611/27/200611/27/2006 1:20:30 PMPPASS
contact: John Stebly; Phone #: ###-#### Internet Inspection Request from: Deb McCoy core walls and stairs ok to cover except elev sconces
ELE06-04352 Rough-In Permanent Service11/27/200611/27/200611/27/2006 10:44:17 AMAPASS
Scheduled by a contractor via Hello! on 11/27/2006 at 6:22:08 AM. Contact: ###-####. ric ok, p/s u/g n ok
ELE06-04177 Electrical Rough-In11/21/200611/27/200611/27/2006 9:53:52 AMACANC
t.j. ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith wrong type request, see rip
ELE06-04177 Rough-In Permanent Service11/27/200611/27/200611/27/2006 9:52:05 AMAPASS
t.j. ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ric ok , p/s o/h n ok
ELE06-03180 Final11/27/200611/27/200611/27/2006 9:14:11 AMAPASS
Scheduled by a contractor via Hello! on 11/27/2006 at 6:20:31 AM. Contact: ###-####. met elect, left survey, nec 408.38 all panelboards shall be deadfront, 210.8(A)(6) shall provide gfci in kitchen, 110.3(B) afci shall trip per mfgrs listing, ok to final
ELE06-03621 Final11/22/200611/27/200611/27/2006 8:17:43 AMAPASS
Please call about 20 minutes prior to inspection, if no one answers please try ###-#### or ###-#### and we will have someone let you in, Thank You; Phone #: ###-#### Internet Inspection Request from: Jamie Winters ok to final
ELE06-04351 Rough-In Permanent Service11/21/200611/27/200611/27/2006 8:03:44 AMACANC
Inspect conduits in concrete for floor outlets; Phone #: ###-#### Internet Inspection Request from: Emmet Bushman called contr, wanted to cancel and recall for pm