Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-01370 FIRE-Final Inspection11/25/200911/27/200911/27/2009 5:00:18 PMAFAIL
The exit discharge lights failed to operate when tested.
FIR09-00030 INSP-Final Inspection11/27/200911/27/200911/27/2009 3:39:27 PMPPART
Permit finaled
FIR09-00440 INSP-Sprinkler Rough-in11/24/200911/27/200911/27/2009 3:39:12 PMAPASS
The previous items on the correction notice have been corrected. The piping still can not be covered until the combustible concealed spaces throughout the facility, including at the fire places have been addressed and the veritical cpvc piping is insulated. These items need to be inspected prior to cover.