Inspections for the day of: Tuesday, November 27, 2012.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-03059 FIRE-Final Inspection11/27/201211/27/201211/27/2012 3:44:43 PMPFAIL
Provide fire extinguisher as discussed and provide the exit signs and emergency lights as shown on the approved plans. Also the deadbolt located on the back door needs to be removed and single action hardware installed.
BLD12-02995 FIRE-Final Inspection11/27/201211/27/201211/27/2012 3:11:42 PMPFAIL
Remove the thumbturn dead bolt from the main exit. Keyed hardware is ok. Provide sticker as discussed. Also remove the round knob at the main exit and provide single action hardware. Provide one 2a, 10bc fire extinguisher with current inspection tag and mount between 5' and 4" above the finish floor in a normal path of travel. Also provide covers on the missing electrical outlets.
FIR12-00638 INSP-Sprinkler Rough-in11/27/201211/27/201211/27/2012 3:02:23 PMPFAIL
Reinspect for the underground failed. No work to correct the bury depth has been performed.
FIR12-00498 INSP-Final Inspection11/27/201211/27/201211/27/2012 1:32:03 PMPPASS
Permit finaled
BLD12-02977 FIRE-Final Inspection11/26/201211/27/201211/27/2012 11:31:21 AMAPASS
Life safety passed
BLD11-03016 FIRE-Final Inspection11/26/201211/27/201211/27/2012 10:07:15 AMAPASS
Life safety passed
BLD12-02087 FIRE-Final Inspection11/26/201211/27/201211/27/2012 10:06:42 AMAPASS
Life safety passed. Temporary suite number was posted
FIR12-00440 INSP-Final Inspection11/26/201211/27/201211/27/2012 9:55:00 AMAPASS
Permit finaled
FIR12-00508 INSP-Final Inspection11/26/201211/27/201211/27/2012 9:54:27 AMAFAIL
When the new smoke detector was tested the strobes activated but the horns/voice evac did not. I verified candella and spacing for the new devices. To pass inspection the audible portion of the fire alarm system needs to function and the heat detector needs to be tested. I also noted three existing smoke detectors located too close to supply/return air grills. This item has been turned over to the fire dept. for follow-up.