ELE09-02259
| ELE-Aging Inspection | 11/27/2013 | 11/27/2013 | 12/2/2013 9:31:06 AM | | DONE |
|
|
Waiting on owner
|
ELE10-01957
| ELE-Aging Inspection | 11/27/2013 | 11/27/2013 | 12/2/2013 9:11:29 AM | | DONE |
|
|
Still under construction
|
ELE13-02791
| Final | 11/27/2013 | 11/27/2013 | 11/27/2013 3:27:18 PM | P | PART |
|
|
Final inspection. Please call Travis Call with any questions ###-#### Phone #: ###-#### >> Inspection requested via web by Clint Tate Some equiptment still needs hooked up. Temp final ok
|
ELE13-02057
| Electrical Rough-In | 11/27/2013 | 11/27/2013 | 11/27/2013 2:53:51 PM | P | PART |
|
|
7th floor ceiling cover. Phone #: ###-#### >> Inspection requested via web by Buster Bowen 300.11- cables shall not be supported by ceiling grid. 330.30 MC cable shall not provide support for other cables. 7th floor ceiling to remain open around stairway. Perimeter ceiling rough in ok cover
|
ELE13-03018
| Final | 11/27/2013 | 11/27/2013 | 11/27/2013 2:24:46 PM | A | NH |
|
|
Phone #: ###-#### >> Inspection requested via web by PAT MILLER No answwer at door
|
ELE13-03261
| Permanent Service | 11/20/2013 | 11/27/2013 | 11/27/2013 2:06:26 PM | P | PASS |
|
|
Moving main service. Mid afternoon inspection requested. Thanks, Eric ###-#### Phone #: ###-#### >> Inspection requested via web by Eric Schroeder p/s o/h rec ok
|
ELE13-02810
| Electrical Rough-In | 11/27/2013 | 11/27/2013 | 11/27/2013 1:45:07 PM | P | PART |
|
|
Inspect for CT Can service, soffit in sales area and parking lot pole bases. Contact is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery Pole bases and sales soffit rough in ok cover. Service 250.24(A)(1)- Grounding electrode conductor connection shall be made at an accessible point and shall terminate at the same bus bar or terminal as the grounded conductor.
|
ELE13-02800
| Electrical Rough-In | 11/26/2013 | 11/27/2013 | 11/27/2013 1:18:54 PM | A | PASS |
|
|
Underground for gas dispensers changed layout of dispensers and conopy Phone #: ###-#### >> Inspection requested via web by Stan Woodward Rough in ok cover
|
ELE13-02922
| Electrical Rough-In | 11/26/2013 | 11/27/2013 | 11/27/2013 12:42:15 PM | P | PASS |
|
|
frank - please call 1 hr prior Phone #: ###-#### Kitchen walls and garage 1/2 wall rough in ok cover
|
ELE13-02710
| Final | 11/26/2013 | 11/27/2013 | 11/27/2013 10:21:20 AM | A | FAIL |
|
|
Final for new home. Should be open. Phone #: ###-#### >> Inspection requested via web by John Edwards 406.11- In all areas specified in 210.52 all 125volt, 15 and 20 amp recepticals shall be listed tamper resistant type. 210.52(D)- A receptical outlet shall be located with in 3' of each basin.
|
ELE13-03002
| Final | 11/26/2013 | 11/27/2013 | 11/27/2013 9:43:32 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Chris Weimar Final ok
|
ELE13-03223
| Electrical Rough-In | 11/26/2013 | 11/27/2013 | 11/27/2013 9:20:43 AM | A | PASS |
|
|
chris Phone #: ###-#### Garage rough in ok cover
|
ELE13-03312
| Permanent Service | 11/26/2013 | 11/27/2013 | 11/27/2013 9:19:20 AM | A | PASS |
|
|
George Phone #: ###-#### Check garage main back fed device is secured on final. Sub feed to garage rough in ok cover
|
ELE13-03324
| Temporary Service | 11/26/2013 | 11/27/2013 | 11/27/2013 8:44:12 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Jay VanSchoiack t/s u/g n ok
|
ELE13-02791
| Final | 11/26/2013 | 11/27/2013 | 11/27/2013 8:16:36 AM | A | NR |
|
|
Final inspection. Please call Travis Call with any questions ###-#### Phone #: ###-#### >> Inspection requested via web by Clint Tate Not ready, panel schedules, device and j-box covers,
|
ELE13-02830
| Electrical Rough-In | 11/26/2013 | 11/27/2013 | 11/27/2013 7:56:20 AM | A | PASS |
|
|
Contact: Wes Powell, wall rough in please Phone #: ###-#### >> Inspection requested via web by Deb Gooden Soffit ceilings rough in ok cover
|
ELE13-02810
| Electrical Rough-In | 11/26/2013 | 11/27/2013 | 11/27/2013 7:47:05 AM | A | CANC |
|
|
Inspect for CT Can, soffit in sales area and parking lot pole bases. Contact is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery Inspection cancelled from web by: Richard Montgomery
|