Inspections for the day of: Wednesday, November 27, 2013.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-02259 ELE-Aging Inspection11/27/201311/27/201312/2/2013 9:31:06 AM DONE
Waiting on owner
ELE10-01957 ELE-Aging Inspection11/27/201311/27/201312/2/2013 9:11:29 AM DONE
Still under construction
ELE13-02791 Final11/27/201311/27/201311/27/2013 3:27:18 PMPPART
Final inspection. Please call Travis Call with any questions ###-#### Phone #: ###-#### >> Inspection requested via web by Clint Tate Some equiptment still needs hooked up. Temp final ok
ELE13-02057 Electrical Rough-In11/27/201311/27/201311/27/2013 2:53:51 PMPPART
7th floor ceiling cover. Phone #: ###-#### >> Inspection requested via web by Buster Bowen 300.11- cables shall not be supported by ceiling grid. 330.30 MC cable shall not provide support for other cables. 7th floor ceiling to remain open around stairway. Perimeter ceiling rough in ok cover
ELE13-03018 Final11/27/201311/27/201311/27/2013 2:24:46 PMANH
Phone #: ###-#### >> Inspection requested via web by PAT MILLER No answwer at door
ELE13-03261 Permanent Service11/20/201311/27/201311/27/2013 2:06:26 PMPPASS
Moving main service. Mid afternoon inspection requested. Thanks, Eric ###-#### Phone #: ###-#### >> Inspection requested via web by Eric Schroeder p/s o/h rec ok
ELE13-02810 Electrical Rough-In11/27/201311/27/201311/27/2013 1:45:07 PMPPART
Inspect for CT Can service, soffit in sales area and parking lot pole bases. Contact is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery Pole bases and sales soffit rough in ok cover. Service 250.24(A)(1)- Grounding electrode conductor connection shall be made at an accessible point and shall terminate at the same bus bar or terminal as the grounded conductor.
ELE13-02800 Electrical Rough-In11/26/201311/27/201311/27/2013 1:18:54 PMAPASS
Underground for gas dispensers changed layout of dispensers and conopy Phone #: ###-#### >> Inspection requested via web by Stan Woodward Rough in ok cover
ELE13-02922 Electrical Rough-In11/26/201311/27/201311/27/2013 12:42:15 PMPPASS
frank - please call 1 hr prior Phone #: ###-#### Kitchen walls and garage 1/2 wall rough in ok cover
ELE13-02710 Final11/26/201311/27/201311/27/2013 10:21:20 AMAFAIL
Final for new home. Should be open. Phone #: ###-#### >> Inspection requested via web by John Edwards 406.11- In all areas specified in 210.52 all 125volt, 15 and 20 amp recepticals shall be listed tamper resistant type.
210.52(D)- A receptical outlet shall be located with in 3' of each basin.
ELE13-03002 Final11/26/201311/27/201311/27/2013 9:43:32 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Chris Weimar Final ok
ELE13-03223 Electrical Rough-In11/26/201311/27/201311/27/2013 9:20:43 AMAPASS
chris Phone #: ###-#### Garage rough in ok cover
ELE13-03312 Permanent Service11/26/201311/27/201311/27/2013 9:19:20 AMAPASS
George Phone #: ###-#### Check garage main back fed device is secured on final. Sub feed to garage rough in ok cover
ELE13-03324 Temporary Service11/26/201311/27/201311/27/2013 8:44:12 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Jay VanSchoiack
t/s u/g n ok
ELE13-02791 Final11/26/201311/27/201311/27/2013 8:16:36 AMANR
Final inspection. Please call Travis Call with any questions ###-#### Phone #: ###-#### >> Inspection requested via web by Clint Tate Not ready, panel schedules, device and j-box covers,
ELE13-02830 Electrical Rough-In11/26/201311/27/201311/27/2013 7:56:20 AMAPASS
Contact: Wes Powell, wall rough in please Phone #: ###-#### >> Inspection requested via web by Deb Gooden Soffit ceilings rough in ok cover
ELE13-02810 Electrical Rough-In11/26/201311/27/201311/27/2013 7:47:05 AMACANC
Inspect for CT Can, soffit in sales area and parking lot pole bases. Contact is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery Inspection cancelled from web by: Richard Montgomery