Inspections for the day of: Friday, November 27, 2015.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-00672 ELE-Aging Inspection11/27/201511/27/201511/27/2015 12:38:19 PM DONE
finaled
ELE10-00672 Final11/27/201511/27/201511/27/2015 12:38:01 PMPPASS
final ok
ELE15-03841 Final11/27/201511/27/201511/27/2015 12:30:41 PMPDONE
We need underground and ok to connect inspections for a manufactured home. Thank you Phone #: ###-#### Inspection requested via web by Thomas Jenkins needed r/i p/s will need intersystem bond termination as per 250.94 at final please label trailer with space number for Idaho power the trailer next to this one says space 8 also ???
ELE15-03841 Rough-In Permanent Service11/27/201511/27/201511/27/2015 12:26:56 PMPPASS
We need underground and ok to connect inspections for a manufactured home. Thank you Phone #: ###-#### Inspection requested via web by Thomas Jenkins r/i u.ground ok p/s o/h rec ok
ELE15-03691 Temporary Service11/25/201511/27/201511/27/2015 9:32:16 AMAFAIL
Inspection requested via web by David McClellan as per 230.24 exhibit 230.20 in hand book 18" minimum required from bottom of drip loop to roof. Tried to call but ###-#### not in service. I think calling for perm. service for each unit would work here. please list address on each main disconnect first. thanks
ELE15-03817 Rough-In Permanent Service11/24/201511/27/201511/27/2015 8:52:51 AMAFAIL
Phone #: ###-#### Inspection requested via web by Alan Lusk ser to c/u hanging below floor joist in garage. recessed can jbox cover laying on the floor in liv. rm., nailplates needed under stairs and at front door wall. Called but could'nt leave message. mailbox full
ELE15-03817 Permanent Service11/27/201511/27/201511/27/2015 8:50:15 AMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk p/s u/g n ok NOTE for contractor: in the future do not mount slip joint coupling to meter base. Once conduit is strapped, slip joint can't do its job
ELE15-03505 Final11/24/201511/27/201511/25/2015 3:04:35 PMACANC
Call Steve with questions Phone #: ###-#### >> Inspection requested via web by Don Lustig Inspection cancelled from web by: Don Lustig