ELE17-03867
| Temporary Service | 11/27/2017 | 11/27/2017 | 11/27/2017 3:32:08 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall Standard 250 breaker exists but has been disconnected. t/s u/g n ok
|
ELE17-03869
| Temporary Service | 11/27/2017 | 11/27/2017 | 11/27/2017 3:11:57 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall 250.53(G)- Ground rod shall be minimum of 8' in length and shall be flush with grade. Rod cut off and is above grade. 312.10(B)- Enclosure shall be of adequate strength. Meter and panel covers missing screws. 590.6(B)- All receptacle outets being used for temp power shall have GFCI protection. 250 GFI present but wiring connected to standard breaker.
|
ELE17-03868
| Temporary Service | 11/27/2017 | 11/27/2017 | 11/27/2017 3:08:28 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall t/s u/g n ok
|
ELE17-03871
| Temporary Service | 11/27/2017 | 11/27/2017 | 11/27/2017 3:07:57 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall t/s u/g n ok
|
ELE17-03873
| Temporary Service | 11/27/2017 | 11/27/2017 | 11/27/2017 3:07:25 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall t/s u/g n ok
|
ELE17-03870
| Temporary Service | 11/27/2017 | 11/27/2017 | 11/27/2017 3:06:43 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall t/s u/g n ok
|
ELE17-03874
| Temporary Service | 11/27/2017 | 11/27/2017 | 11/27/2017 3:06:11 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall t/s u/g n ok
|
ELE17-03875
| Temporary Service | 11/27/2017 | 11/27/2017 | 11/27/2017 3:05:34 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall t/s u/g n ok
|
ELE17-01337
| Electrical Rough-In | 11/22/2017 | 11/27/2017 | 11/27/2017 2:16:51 PM | P | PASS |
|
|
We are requesting a rough-in inspection for 5th floor west side and 1st floor mechanical room walls for Monday Nov. 27th in the afternoon. Our contact is Rick @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate 519 thru 534 and storage walls and west corridor ceiling, 1st floor mechanical room walls only rough in ok cover
|
ELE17-02732
| Electrical Rough-In | 11/27/2017 | 11/27/2017 | 11/27/2017 12:54:11 PM | P | PASS |
|
|
As early as possible please. Phone #: ###-#### Inspection requested via web by Kerri Hamilton Boarders ok to install in offices and common areas except IT room 804. Grid rough in for south west area only as noted on contractor print. 3 warnings have been given for covering any areas prior to inspection, future issues will result in complete removal of areas covered in question.
|
ELE17-03965
| Conference | 11/22/2017 | 11/27/2017 | 11/27/2017 12:32:36 PM | P | DONE |
|
|
please call to arrange time // Warren Phone #: ###-#### Discussed the required clearance for overhead service entrance conductors over a hot tub located under a covered outdoor area. Location of tub is not completely enclosed so still concidered an outdoor installation. There is no exceptions listed for overhead clearances. Minimum required by 680.9(A) shall apply.
|
ELE17-03864
| Final | 11/21/2017 | 11/27/2017 | 11/27/2017 9:52:55 AM | A | PASS |
|
|
The homeowner will be home but would like a call on your way please, Beverly ###-####. If you have any questions please call Andrew ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan Final ok
|
ELE17-03864
| Electrical Rough-In | 11/21/2017 | 11/27/2017 | 11/27/2017 9:51:46 AM | A | PASS |
|
|
The homeowner will be home but would like a call on your way, Beverly ###-####. If you have any questions please call Andrew ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan Water heater rough in ok cover
|
ELE17-03975
| Electrical Rough-In | 11/26/2017 | 11/27/2017 | 11/27/2017 9:08:43 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Robert Murray Rough in ok cover
|
ELE17-03975
| Permanent Service | 11/27/2017 | 11/27/2017 | 11/27/2017 9:08:20 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Robert Murray p/s u/g n ok
|