Inspections for the day of: Monday, November 27, 2017.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03867 Temporary Service11/27/201711/27/201711/27/2017 3:32:08 PMPPASS
Phone #: ###-#### Inspection requested via web by Todd Hall
Standard 250 breaker exists but has been disconnected. t/s u/g n ok
ELE17-03869 Temporary Service11/27/201711/27/201711/27/2017 3:11:57 PMPFAIL
Phone #: ###-#### Inspection requested via web by Todd Hall
250.53(G)- Ground rod shall be minimum of 8' in length and shall be flush with grade. Rod cut off and is above grade.
312.10(B)- Enclosure shall be of adequate strength. Meter and panel covers missing screws.
590.6(B)- All receptacle outets being used for temp power shall have GFCI protection.
250 GFI present but wiring connected to standard breaker.
ELE17-03868 Temporary Service11/27/201711/27/201711/27/2017 3:08:28 PMPPASS
Phone #: ###-#### Inspection requested via web by Todd Hall
t/s u/g n ok
ELE17-03871 Temporary Service11/27/201711/27/201711/27/2017 3:07:57 PMPPASS
Phone #: ###-#### Inspection requested via web by Todd Hall
t/s u/g n ok
ELE17-03873 Temporary Service11/27/201711/27/201711/27/2017 3:07:25 PMPPASS
Phone #: ###-#### Inspection requested via web by Todd Hall
t/s u/g n ok
ELE17-03870 Temporary Service11/27/201711/27/201711/27/2017 3:06:43 PMPPASS
Phone #: ###-#### Inspection requested via web by Todd Hall
t/s u/g n ok
ELE17-03874 Temporary Service11/27/201711/27/201711/27/2017 3:06:11 PMPPASS
Phone #: ###-#### Inspection requested via web by Todd Hall
t/s u/g n ok
ELE17-03875 Temporary Service11/27/201711/27/201711/27/2017 3:05:34 PMPPASS
Phone #: ###-#### Inspection requested via web by Todd Hall
t/s u/g n ok
ELE17-01337 Electrical Rough-In11/22/201711/27/201711/27/2017 2:16:51 PMPPASS
We are requesting a rough-in inspection for 5th floor west side and 1st floor mechanical room walls for Monday Nov. 27th in the afternoon. Our contact is Rick @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate
519 thru 534 and storage walls and west corridor ceiling, 1st floor mechanical room walls only rough in ok cover
ELE17-02732 Electrical Rough-In11/27/201711/27/201711/27/2017 12:54:11 PMPPASS
As early as possible please. Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Boarders ok to install in offices and common areas except IT room 804. Grid rough in for south west area only as noted on contractor print. 3 warnings have been given for covering any areas prior to inspection, future issues will result in complete removal of areas covered in question.
ELE17-03965 Conference11/22/201711/27/201711/27/2017 12:32:36 PMPDONE
please call to arrange time // Warren Phone #: ###-####
Discussed the required clearance for overhead service entrance conductors over a hot tub located under a covered outdoor area. Location of tub is not completely enclosed so still concidered an outdoor installation. There is no exceptions listed for overhead clearances. Minimum required by 680.9(A) shall apply.
ELE17-03864 Final11/21/201711/27/201711/27/2017 9:52:55 AMAPASS
The homeowner will be home but would like a call on your way please, Beverly ###-####. If you have any questions please call Andrew ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan Final ok
ELE17-03864 Electrical Rough-In11/21/201711/27/201711/27/2017 9:51:46 AMAPASS
The homeowner will be home but would like a call on your way, Beverly ###-####. If you have any questions please call Andrew ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan
Water heater rough in ok cover
ELE17-03975 Electrical Rough-In11/26/201711/27/201711/27/2017 9:08:43 AMAPASS
Phone #: ###-#### Inspection requested via web by Robert Murray
Rough in ok cover
ELE17-03975 Permanent Service11/27/201711/27/201711/27/2017 9:08:20 AMPPASS
Phone #: ###-#### Inspection requested via web by Robert Murray p/s u/g n ok