Inspections for the day of: Tuesday, November 27, 2018.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-04590 FIRE-Conference11/27/201811/27/201811/27/2018 1:47:04 PMPDONE
Randy and I went over basic life safety requirements for his project.
BLD18-01809 FIRE-Final Inspection11/26/201811/27/201811/27/2018 1:46:17 PMAFAIL
Life safety will be ok to pass when the project related fire alarm permit is finaled

ceil Phone #: ###-####
FIR18-00648 INSP-Final Inspection11/27/201811/27/201811/27/2018 11:37:04 AMAFAIL
Relocate the smoke detector for door release to center of the door and repair the fire smoke damper and re-test.

Phone #: ###-#### Inspection requested via web by Gary Gambino
FIR18-00642 INSP-Final Inspection11/26/201811/27/201811/27/2018 11:26:35 AMAFAIL
Todays inspection was just for the notification devices. See the city approved plans for the devices overspaced or mounted too high. Not all of the devices have been checked for the correct candella. Contractor will need to contact plan review on whether a plan mod is needed or just as-builts. Also the fire doors did not close when the smoke detectors were tested.


Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
FIR18-00864 INSP-Sprinkler Rough-in11/26/201811/27/201811/27/2018 10:26:13 AMAPASS
Piping above hardlids is ok for cover.

Mike Phone #: ###-####