BLD17-04590
| FIRE-Conference | 11/27/2018 | 11/27/2018 | 11/27/2018 1:47:04 PM | P | DONE |
|
|
Randy and I went over basic life safety requirements for his project.
|
BLD18-01809
| FIRE-Final Inspection | 11/26/2018 | 11/27/2018 | 11/27/2018 1:46:17 PM | A | FAIL |
|
|
Life safety will be ok to pass when the project related fire alarm permit is finaled
ceil Phone #: ###-####
|
FIR18-00648
| INSP-Final Inspection | 11/27/2018 | 11/27/2018 | 11/27/2018 11:37:04 AM | A | FAIL |
|
|
Relocate the smoke detector for door release to center of the door and repair the fire smoke damper and re-test.
Phone #: ###-#### Inspection requested via web by Gary Gambino
|
FIR18-00642
| INSP-Final Inspection | 11/26/2018 | 11/27/2018 | 11/27/2018 11:26:35 AM | A | FAIL |
|
|
Todays inspection was just for the notification devices. See the city approved plans for the devices overspaced or mounted too high. Not all of the devices have been checked for the correct candella. Contractor will need to contact plan review on whether a plan mod is needed or just as-builts. Also the fire doors did not close when the smoke detectors were tested.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
FIR18-00864
| INSP-Sprinkler Rough-in | 11/26/2018 | 11/27/2018 | 11/27/2018 10:26:13 AM | A | PASS |
|
|
Piping above hardlids is ok for cover.
Mike Phone #: ###-####
|