ELE01-02076
| ELE-Aging Inspection | 11/28/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | | PASS |
|
|
|
ELE01-00569
| ELE-Aging Inspection | 11/28/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | | PASS |
|
|
ok 11/28/2001 10:31:59 AM
|
ELE01-01726
| ELE-Aging Inspection | 11/28/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | | CANC |
|
|
|
ELE01-03355
| ELE-Aging Inspection | 11/28/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | | PART |
|
|
suc 11/28/2001 9:37:47 AM
|
ELE01-02170
| ELE-Aging Inspection | 11/28/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | | PASS |
|
|
11/28/2001 11:03:30 AM what Icould see looked ok 11/28/2001 11:03:30 AM 11/28/2001 11:04:02 AM 11/28/2001 11:04:43 AM
|
ELE01-03349
| ELE-Aging Inspection | 11/28/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | | PART |
|
|
suc 11/28/2001 9:34:26 AM
|
ELE01-00385
| ELE-Aging Inspection | 11/28/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | | PART |
|
|
suc Mitchell will call when ready 11/28/2001 9:36:09 AM
|
ELE01-02672
| ELE-Aging Inspection | 11/28/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | | PART |
|
|
stopped at job site still under const. 11/30/2001 10:17:45 AM
|
ELE01-02838
| ELE-Aging Inspection | 11/28/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | | DONE |
|
|
|
ELE01-00310
| ELE-Aging Inspection | 11/28/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | | PASS |
|
|
new permit was secured for job 11/28/2001 11:09:08 AM
|
ELE01-00506
| ELE-Aging Inspection | 11/28/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | | PART |
|
|
called left message to have homeowner call me about status of job 12/3/2001 5:19:31 PM
|
ELE01-01409
| ELE-Aging Inspection | 11/28/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | | PART |
|
|
SUC 11/28/2001 10:34:01 AM
|
ELE01-03042
| ELE-Aging Inspection | 11/28/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | | PART |
|
|
called Tri State they said job is complete, and they will call for inspection 12/3/2001 4:56:49 PM
|
ELE01-02928
| ELE-Aging Inspection | 11/28/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | | PART |
|
|
job still under construction 11/28/2001 10:36:01 AM
|
ELE01-02957
| ELE-Aging Inspection | 11/28/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | | PASS |
|
|
ok 11/28/2001 11:05:11 AM
|
ELE01-03658
| Final | 11/27/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | A | PASS |
|
|
wendy ###-#### ok 11/28/2001 10:29:26 AM
|
ELE01-03805
| Electrical Rough-In | 11/27/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/27/2001 at 11:28:01. Contact: ###-####. r/i ok 11/28/2001 11:26:07 AM
|
ELE01-00937
| Final | 11/28/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 11/28/2001 at 10:05:38. Contact: ###-####. need 600 volt rated wire for phone in elevator cabinet, lables for both elevator disconnects,and elevator light disconnect shall have grounded conductor terminate in disconnect,anb in offset nipple 300-3 called message said no sevice at this time 11/28/2001 3:32:59 PM
|
ELE01-00342
| Permanent Service | 11/28/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | P | NH |
|
|
andy ###-#### called Andy arrange for access and call inspection when done 11/28/2001 3:05:46 PM
|
ELE01-03829
| Final | 11/28/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | P | FAIL |
|
|
###-#### kathy this is for a p/s corrections noted to contractor by phone problen deration of over 3 current carrying conductors in a raceway 310-15, and 250-148 electrician did not have any idea of what I explained to him will have to meet with him 11/28/2001 5:03:42 PM
|
ELE01-02815
| Electrical Rough-In | 11/28/2001 | 11/28/2001 | 11/28/2001 12:00:00 AM | P | PART |
|
|
Added by Inspector: 315 On 11/28/2001 4:16:52 PM conference with Power Electric about GEC
|