Inspections for the day of: Wednesday, November 28, 2001.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE01-02076 ELE-Aging Inspection11/28/200111/28/200111/28/2001 12:00:00 AM PASS
ELE01-00569 ELE-Aging Inspection11/28/200111/28/200111/28/2001 12:00:00 AM PASS
ok 11/28/2001 10:31:59 AM
ELE01-01726 ELE-Aging Inspection11/28/200111/28/200111/28/2001 12:00:00 AM CANC
ELE01-03355 ELE-Aging Inspection11/28/200111/28/200111/28/2001 12:00:00 AM PART
suc 11/28/2001 9:37:47 AM
ELE01-02170 ELE-Aging Inspection11/28/200111/28/200111/28/2001 12:00:00 AM PASS
11/28/2001 11:03:30 AM what Icould see looked ok 11/28/2001 11:03:30 AM 11/28/2001 11:04:02 AM 11/28/2001 11:04:43 AM
ELE01-03349 ELE-Aging Inspection11/28/200111/28/200111/28/2001 12:00:00 AM PART
suc 11/28/2001 9:34:26 AM
ELE01-00385 ELE-Aging Inspection11/28/200111/28/200111/28/2001 12:00:00 AM PART
suc Mitchell will call when ready 11/28/2001 9:36:09 AM
ELE01-02672 ELE-Aging Inspection11/28/200111/28/200111/28/2001 12:00:00 AM PART
stopped at job site still under const. 11/30/2001 10:17:45 AM
ELE01-02838 ELE-Aging Inspection11/28/200111/28/200111/28/2001 12:00:00 AM DONE
ELE01-00310 ELE-Aging Inspection11/28/200111/28/200111/28/2001 12:00:00 AM PASS
new permit was secured for job 11/28/2001 11:09:08 AM
ELE01-00506 ELE-Aging Inspection11/28/200111/28/200111/28/2001 12:00:00 AM PART
called left message to have homeowner call me about status of job 12/3/2001 5:19:31 PM
ELE01-01409 ELE-Aging Inspection11/28/200111/28/200111/28/2001 12:00:00 AM PART
SUC 11/28/2001 10:34:01 AM
ELE01-03042 ELE-Aging Inspection11/28/200111/28/200111/28/2001 12:00:00 AM PART
called Tri State they said job is complete, and they will call for inspection 12/3/2001 4:56:49 PM
ELE01-02928 ELE-Aging Inspection11/28/200111/28/200111/28/2001 12:00:00 AM PART
job still under construction 11/28/2001 10:36:01 AM
ELE01-02957 ELE-Aging Inspection11/28/200111/28/200111/28/2001 12:00:00 AM PASS
ok 11/28/2001 11:05:11 AM
ELE01-03658 Final11/27/200111/28/200111/28/2001 12:00:00 AMAPASS
wendy ###-#### ok 11/28/2001 10:29:26 AM
ELE01-03805 Electrical Rough-In11/27/200111/28/200111/28/2001 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 11/27/2001 at 11:28:01. Contact: ###-####. r/i ok 11/28/2001 11:26:07 AM
ELE01-00937 Final11/28/200111/28/200111/28/2001 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 11/28/2001 at 10:05:38. Contact: ###-####. need 600 volt rated wire for phone in elevator cabinet, lables for both elevator disconnects,and elevator light disconnect shall have grounded conductor terminate in disconnect,anb in offset nipple 300-3 called message said no sevice at this time 11/28/2001 3:32:59 PM
ELE01-00342 Permanent Service11/28/200111/28/200111/28/2001 12:00:00 AMPNH
andy ###-#### called Andy arrange for access and call inspection when done 11/28/2001 3:05:46 PM
ELE01-03829 Final11/28/200111/28/200111/28/2001 12:00:00 AMPFAIL
###-#### kathy this is for a p/s corrections noted to contractor by phone problen deration of over 3 current carrying conductors in a raceway 310-15, and 250-148 electrician did not have any idea of what I explained to him will have to meet with him 11/28/2001 5:03:42 PM
ELE01-02815 Electrical Rough-In11/28/200111/28/200111/28/2001 12:00:00 AMPPART
Added by Inspector: 315 On 11/28/2001 4:16:52 PM conference with Power Electric about GEC