Inspections for the day of: Friday, November 28, 2003.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-02622 FIRE-Final Inspection11/26/200311/28/200311/28/2003 12:00:00 AMAPASS
jack; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie shell okay; RTU is under 2000 cfm and detection for shut down is not required; no smoke detectors were installed as shown on plans 11/28/2003 10:35:29 AM
BLD03-01837 FIRE-Final Inspection11/26/200311/28/200311/28/2003 12:00:00 AMAFAIL
joan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore need address; fire extinguishers at both levels; NE exit must be openable from the inside without special knowledge and SE exit has deadbolt to be removed; stagjing exit to be lever type; need duct detectors for AC 1 and 2 with remote indicators; need "Door to Remian unlocked..." above main exit double doors 11/28/2003 11:33:21 AM
BLD03-01732 FIRE-Final Inspection11/28/200311/28/200311/28/2003 12:00:00 AMAPART
temp occupancy for fire/life safety is approved per Dave Miller pending resolution of the fire alarm system; this TI space has improper notification device (horn) and several spot detectors; the FACP is in the fire station and it appeared to be in trouble; the TI space will have to be brought up to code or removal as the space isn't required an alarm system
BLD03-02623 FIRE-Final Inspection11/28/200311/28/200311/28/2003 12:00:00 AMAPART
temp occupancy approved per Dave Miller until the extinguishing system is connected to sprinkler monitoring panel as all other items from previous inspection have been completed 11/28/2003 11:55:03 AM
BLD03-01362 FIRE-Final Inspection11/28/200311/28/200311/28/2003 12:00:00 AMPFAIL
DAVE; Phone #: ###-#### Internet Inspection Request from: Darla Downs landing needed at new exit door; need to test the fire alarms - the detectors added in this space will need to be moved to the deck as they are on the bottom cord of the trusses 11/28/2003 2:04:08 PM