Inspections for the day of: Wednesday, November 28, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-03088 FIRE-Final Inspection11/27/200711/28/200711/28/2007 5:06:57 PMAFAIL
Missing required fire extinguishers at the cleanroom area, one wall mounted av needs to be reinstalled, need project related fire alarm permit final. EM lighting and exit signs tested acceptable, remainder of fire life safety items are satisfactory.
FIR06-00940 INSP-Final Inspection11/28/200711/28/200711/28/2007 5:03:45 PMPPASS
Fire sprinkler passed final inspection.
FIR07-00205 INSP-Final Inspection11/28/200711/28/200711/28/2007 5:02:37 PMPPASS
Corrections verified for completion, fire sprinkler permit finaled.
FIR06-00504 INSP-Final Inspection11/27/200711/28/200711/28/2007 3:18:05 PMANR
FIR07-00129 INSP-Final Inspection11/28/200711/28/200711/28/2007 2:11:03 PMPDEFR
See inspection comments per M. Timmerman.
FIR07-00333 INSP-Final Inspection11/27/200711/28/200711/28/2007 2:10:22 PMADEFR
See inspection comments per M. Timmerman.
FIR07-00481 INSP-Supply line flush11/26/200711/28/200711/28/2007 11:54:16 AMAPART
Underground flush passed.As per KR
BLD07-01778 FIRE-Final Inspection11/27/200711/28/200711/28/2007 11:18:51 AMAFAIL
Missing exit sign above door. When building is locked down mag locks on main entrance south side will not release when aproached from egress side, sensor were not installed.
Noted they need to follow steps from 2003 IFC chapter 10, 1008.1.3.4 all 6 steps. Noted on plans. Doors will release on fire alarm. as per KR
FIR07-00108 FIR-Aging Inspection11/28/200711/28/200711/28/2007 11:09:42 AM DEFR
Pending inspection request.
FIR07-00729 INSP-Final Inspection11/28/200711/28/200711/28/2007 11:06:45 AMPPASS
Fire sprinkler work is complete, noted one missing escutcheon at the north corridor to be installed today.
FIR07-00661 INSP-Final Inspection11/28/200711/28/200711/28/2007 11:04:39 AMAPASS
Final inspection passed, field modifications are approved, permit finaled.
FIR07-00955 INSP-Final Inspection11/28/200711/28/200711/28/2007 11:03:33 AMAPASS
OH modifications passed field inspections, fire sprinkler permit finaled.
FIR07-00613 INSP-Final Inspection11/28/200711/28/200711/28/2007 11:02:21 AMAPASS
Fire sprinkler demo work is complete, permit finaled.
BLD07-00017 FIRE-Final Inspection11/27/200711/28/200711/28/2007 11:01:24 AMAPASS
Fire life safety is acceptable, c/n items are complete except approved door hardware at two locations (wash bay and SE mech. room) to be installed as discussed prior to structural final, also noted one exit sign to be removed at the east side of the truckers lounge.