Inspections for the day of: Wednesday, November 28, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMike Kinnear
TitleELE-INSPECTOR
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03657 Electrical Rough-In11/28/200711/28/200711/28/2007 5:04:54 PMPFAIL
linda - please call 1/2 hr prior to inspection Phone #: ###-#### home owner did not do the work she staed that she would get an electrical contractor to complete the job. note service change is incorrect needs two ground rods, ground water system, put grounding electrode conductor & grounded conductor on same bus bar, proper breakers for wire size, boxes for lights over bathrm vanity, & all grounding condutors in boxes shall tied together.
ELE07-03511 Final11/28/200711/28/200711/28/2007 4:32:15 PMPPASS
alan Phone #: ###-#### ok final
ELE07-03932 Electrical Rough-In11/27/200711/28/200711/28/2007 3:35:56 PMAPEND
Please call at least 30 mins prior to inspection--lyndon Phone #: ###-#### electrical contractor that did the work needs to get a permit for the work done. the electrical that took this permit is aware there will be no refund.
ELE07-03729 Final11/28/200711/28/200711/28/2007 2:12:56 PMPCANC
call ###-#### for access code. We need a final ceiling inspection. Phone #: ###-#### Internet Inspection Request from: Alison Pennington wrong type of inspection
ELE07-03729 Electrical Rough-In11/28/200711/28/200711/28/2007 2:12:26 PMPPASS
call ###-#### for access code. We need a final ceiling inspection. Phone #: ###-#### Internet Inspection Request from: Alison Pennington ok cover ceiling only
ELE07-03706 Electrical Rough-In11/28/200711/28/200711/28/2007 2:11:42 PMPFAIL
robert Note: cover ceiling tile Phone #: ###-#### correction nec330.30(B) cable shall be supported within 12inch of all boxes
ELE07-03414 Final11/28/200711/28/200711/28/2007 1:08:18 PMPPASS
Contact is Jay Sprik. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery ok final
ELE07-00511 Final11/27/200711/28/200711/28/2007 11:53:03 AMAPASS
mike Phone #: ###-#### ok final
ELE07-03922 Electrical Rough-In11/27/200711/28/200711/28/2007 10:13:40 AMAPASS

DAVE BRADSHAW - CALL IF THERE ARE ANY QUESTIONS - UFER GROUND Phone #: ###-#### Internet Inspection Request from: Randy Vail ok cover grounding conductor
ELE07-01391 Final11/26/200711/28/200711/28/2007 10:12:55 AMAPASS
CONTACT: MARK KNIGHT Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok final note signed card
ELE07-03414 Final11/27/200711/28/200711/28/2007 8:51:25 AMANR
jay Phone #: ###-#### arcfault will not reset & no furnace disconnect