Inspections for the day of: Wednesday, November 28, 2012.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01993 Final11/28/201211/28/201211/28/2012 1:14:00 PMPPART
Dave Baugh on site. Phone #: ###-#### >> Inspection requested via web by Clint Tate met contractor, signed t/o card, shall securely strap flex raceway within 12" of termination, shall label disconnects, shall enclose conductor in raceway for fixtures
ELE12-02880 Temporary Service11/28/201211/28/201211/28/2012 12:15:45 PMPPASS
Call Dene with any questions
Thank you Phone #: ###-#### >> Inspection requested via web by kim grundhauser t/s u/g n ok
ELE12-02677 Final11/27/201211/28/201211/28/2012 10:19:47 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Andy Derrick ok final
ELE12-02761 Final11/27/201211/28/201211/28/2012 9:59:18 AMAPASS
paul Phone #: ###-#### ok final, no card
ELE12-02853 Electrical Rough-In11/27/201211/28/201211/28/2012 9:17:38 AMAPASS
Please call ahead for access.
Kelly-###-#### Phone #: ###-#### >> Inspection requested via web by William Andrews ok cover floor heat only, shall see wiring from panel later
ELE12-02876 Electrical Rough-In11/27/201211/28/201211/28/2012 8:57:12 AMAPART
not before 8:30, thanks Phone #: ###-#### >> Inspection requested via web by Andy Derrick front rooms and back areas main floor only ok, do basement and kitchen later
ELE12-00535 Final11/27/201211/28/201211/28/2012 8:14:10 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Clint Tate ok final, no card