PDS Online
Making
Boise
the most livable city in the country.
Home
Permits
Search by Permit Number
How to search by permit number
Search by Address
Search by Customer Number
Search by Current Planning Number
Search in Project by Permit Number
Search by Project Name
Inspections
Search by Permit Number
Search by Request Date
Search by Company Name
Fees
Impact Fees Estimate Calculator
Other Searches
Search for Licensed Contractors
Search Parcel by Address
Search Historical Surveys
Reports
Daily Reports
Weekly Reports
Monthly Reports
Home
/
Inspections
/
Inspector Activity
Inspections for the day of:
Wednesday, November 28, 2012
.
Number of inspections:
12
Percentage of inspections complete:
100 %
Percentage of inspections not complete:
0 %
Contact Information
Inspector
Forrest France
Title
FIRE INSPECTOR
Phone #
794-1981
Permit Number
Description
Received
Requested
Completed
AM/PM
Disposition
FIR06-00385
FIR-Aging Inspection
11/28/2012
11/28/2012
11/29/2012 7:25:22 PM
DEFR
FIR05-00238
FIR-Aging Inspection
11/28/2012
11/28/2012
11/29/2012 7:24:51 PM
DEFR
FIR07-00315
FIR-Aging Inspection
11/28/2012
11/28/2012
11/29/2012 7:24:29 PM
DEFR
FIR12-00434
INSP-Final Inspection
11/28/2012
11/28/2012
11/29/2012 6:25:14 AM
P
PART
Completed initial walkthrough. Items noted include five non-functional HD to be removed, add visual coverage per plan review red-lines at the second floor corridor building A, provide coverage at the maintenance work room building C 1st floor, post a legible points map at the panel. Discussed remainder of test schedule.
FIR12-00318
INSP-Final Inspection
11/28/2012
11/28/2012
11/29/2012 6:14:59 AM
P
NR
Final pending project related fire alarm testing for riser supervision. Also need to complete forward flow test.
FIR12-00318
INSP-Sprinkler Rough-in/Hydro
11/28/2012
11/28/2012
11/29/2012 6:13:31 AM
P
PART
Overhead hydrostatic test completed satisfactory. Need to add baffles per approved plan.
FIR12-00501
INSP-Final Inspection
11/28/2012
11/28/2012
11/28/2012 2:10:04 PM
P
PASS
BLD12-01930
FIRE-Final Inspection
11/27/2012
11/28/2012
11/28/2012 2:09:01 PM
A
PASS
Fire life safety passed. Door hardware at room 222 to be completed prior to structural final as discussed.
FIR12-00562
INSP-Final Inspection
11/28/2012
11/28/2012
11/28/2012 2:05:43 PM
P
PASS
Fire sprinkler permit finaled.
BLD12-02613
FIRE-Final Inspection
11/26/2012
11/28/2012
11/28/2012 2:03:35 PM
A
PASS
FIR12-00484
INSP-Final Inspection
11/28/2012
11/28/2012
11/28/2012 2:02:19 PM
A
PASS
FIR12-00553
INSP-Final Inspection
11/28/2012
11/28/2012
11/28/2012 2:01:43 PM
A
PASS