Inspections for the day of: Wednesday, November 28, 2012.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00550 INSP-Sprinkler Rough-in11/28/201211/28/201211/28/2012 3:39:33 PMPPART
See the city approved plans for locations marked "ok" where the ceiling tile can be installed. Per Tim Frost branchline restraints are not required in this area.
FIR12-00559 INSP-Final Inspection11/28/201211/28/201211/28/2012 3:07:27 PMPPASS
permit finaled
BLD12-02657 FIRE-Final Inspection11/28/201211/28/201211/28/2012 2:09:59 PMPPART
A 30 day temporary occupancy was given with Scott and Jason's permission until the remaining portion of the tenant work is completed and finaled. The finished side of the tenant space is to be secured from the "construction side" of the tenant space.
BLD12-02649 FIRE-Final Inspection11/27/201211/28/201211/28/2012 11:01:35 AMAPASS
Life safety passed
BLD12-02657 FIRE-Conference11/28/201211/28/201211/28/2012 9:51:19 AMAFAIL
Mount and tag fire extinguisheres as discussed. Provide single action hardware as per the Accessibility notes on sheet A0.0. Finish all construction as shown on the approved drawings.