Inspections for the day of: Friday, November 28, 2014.
Number of inspections: 9
Percentage of inspections complete: 67 %
Percentage of inspections not complete: 33 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00735 INSP-Sprinkler Rough-in11/24/201411/25/2014 A 
RTC for Dry System, Bldg D 1st floor, please call Scott 30 minutes prior at ###-#### Phone #: ###-#### >> Inspection requested via web by Jacci Hunt
FIR14-00708 INSP-Sprinkler Rough-in11/26/201411/26/2014 P 
Matt Phone #: ###-####
FIR14-00531 INSP-Conference11/26/201411/26/2014 P 
Nate is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
FIR14-00840 INSP-Sprinkler Rough-in11/28/201411/28/201411/28/2014 4:32:49 PMPPART
OH rough-in inspection completed satisfactory.
BLD14-03388 FIRE-Final Inspection11/28/201411/28/201411/28/2014 1:32:40 PMPPASS
Life safety approved pending "door to remain...." signage is posted at the main entry/exit. To be completed prior to structural final as discussed with Linda.
BLD14-02862 FIRE-Final Inspection11/28/201411/28/201411/28/2014 1:30:52 PMPFAIL
Project is not in condition for final approval at this time. Noted several items including; missing panic hardware at the meeting room exit doors per plan, post max. occupant signage, provide second exit sign/EM light at the meeting room per plan, missing ceiling tile throughout, provide approved hardware at the restroom door, repair exit discharge light at the alley way, missing hardware at the second exit from meeting room, post fire extinguishers per plan, project related fire sprinkler permit is not yet finaled, remove non-applicable suite address numbers, blank or disable keyed deadbolt above panic hardware main entry/exit.
BLD13-02118 FIRE-Final Inspection11/28/201411/28/201411/28/2014 11:42:55 AMAPASS
Verified C/N items. Fire life safety finaled.
BLD14-01045 FIRE-Final Inspection11/28/201411/28/201411/28/2014 10:47:30 AMAPASS
Fire life safety inspection passed provided door hardware at the SW exit is reversed to allow free egress as discussed- to be finished prior to structural final for verification at that time.
BLD14-01339 FIRE-Final Inspection11/28/201411/28/201411/28/2014 10:27:38 AMANR
Inspection request intended for Monday 12/1 AM per conversation with the contractor. -Rescheduled per discussion